13. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge suppressor
The recommended surge suppressor for installation to an AC relay, AC valve, AC electromagnetic
brake or the like near the servo amplifier is shown below. Use this product or equivalent.
Surge suppressor
Surge suppressor
Rated
voltage
C [ F]
R [ ]
AC[V]
50
200
0.5
(1W)
Note that a diode should be installed to a DC relay, DC valve or
the like.
Maximum voltage: Not less than 4 times the drive voltage of
Maximum current: Not less than twice the drive current of
(c) Cable clamp fitting (AERSBAN
Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown
below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath
to expose the external conductor, and press that part against the earth plate with the cable clamp.
If the cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.
Strip the cable sheath of
the clamped area.
MS
Test voltage AC[V]
Across
T-C 1000(1 to 5s)
the relay or the like
the relay or the like
-SET)
cutter
cable
Relay
(Ex.) 972A.2003 50411
(Matsuo Electric Co.,Ltd. 200VAC rating)
Outline drawing [Unit: mm] ([Unit: in.])
Vinyl sheath
Blue vinyl cord
10(0.39)or less
10 3
15 1(0.59 0.04)
(0.39
0.12)
200(7.87)
48 1.5
or more
(1.89 0.06)
Clamp section diagram
13 - 27
Surge suppressor
This distance should be short
(within 20cm(0.79 in.)).
Red vinyl cord
6(0.24)
10(0.39)or less
10 3
(0.39
0.15)
200(7.87)
or more
RA
Diode
Cable
Cable clamp
(A,B)
External conductor
18 1.5
(0.71 0.06)
4(0.16)
31(1.22)
Earth plate