9.1 Indoor Unit Error Display

Operation
Timer lamp
lamp
☆ 1 time
☆ 2 times
☆ 3 times
☆ 4 times
☆ 5 times
☆ 6 times
☆ 7 times
☆ 1 times
☆ 2 times
☆ 3 times
☆ 4 times
☆ 5 times
☆ 6 times
☆ 1 times
☆ 2 times
☆ 3 times
☆ 5 times
Display
LED STATUS
X
E0
Indoor unit EEPROM parameter error
X
E1
Indoor / outdoor units communication error
Zero-crossing signal detection error(only for
X
E2
MS12F-12CRDN1-MP0W, MS12F-18CRDN1-NC2W,
MS12F-22CRDN1-MP5W)
X
E3
Indoor fan speed has been out of control
Indoor room temperature sensor T1 open circuit or short
X
E4
circuit
Evaporator coil temperature sensor T2 open circuit or
X
E5
short circuit
X
EC
Refrigerant leakage detection
O
F0
Overload current protection
Outdoor ambient temperature sensor T4 open circuit or
O
F1
short circuit
Condenser coil temperature sensor T3 open circuit or
O
F2
short circuit
Compressor discharge temperature sensor T5 open
O
F3
circuit or short circuit
O
F4
Outdoor unit EEPROM parameter error
O
F5
Outdoor fan speed has been out of control
P0
IPM malfunction or IGBT over-strong current protection
P1
Over voltage or over low voltage protection
High temperature protection of compressor top
P2
diagnosis and solution
P4
Inverter compressor drive error
O(light)
X(off)
☆(flash)
27