Connect Pipes; Indoor Unit - Pioneer WAS series Installation Manual

Split-type
Hide thumbs Also See for WAS series:
Table of Contents

Advertisement

6. Place aring tool onto the form.
7. Turn the handle of the aring tool clockwise
until the pipe is fully ared.
8. Remove the aring tool and are form, then
inspect the end of the pipe for cracks and
even aring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful
not to use excessive torque or to deform the
piping in any way. You should first connect the
low-pressure pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping,
the minimum bending radius is 10cm. See Fig
5.6 .
Radius
Fig. 5.6
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 0.25")
Ø 9.52 (Ø 0.375")
Ø 12.7 ( Ø 0.5")
Ø 16 ( Ø 0.63")
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque
requirements shown in the table above.
≥10cm (4in)
TORQUE REQUIREMENTS
Tightening Torque (N•cm)
1,500 (11lb • ft)
2,500 (18.4lb • ft)
3,500 (25.8lb•ft)
4,500 (33.19lb•ft)
Instructions for Connecting Piping to

Indoor Unit

1. Align the center of the two pipes that you will
connect. See Fig. 5.7 .
Indoor unit tubing
Fig. 5.7
2. Tighten the are nut as tightly as possible by
hand.
3. Using a spanner, grip the nut on the unit
tubing.
4. While rmly gripping the nut on the unit
tubing, use a torque wrench to tighten the
are nut according to the torque values in the
Torque Requirements
the aring nut slightly, then tighten again.
Fig. 5.8
Add. Tightening Torque (N•m)
Flare nut
Pipe
table below. Loosen
1,600 (11.8lb • ft)
2,600 (19.18lb • ft)
3,600 (26.55lb•ft)
4,700 (34.67lb•ft)
Page 27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wys series

Table of Contents