Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully. LA-ON-RACK 6K/10K...
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ....................3 1.1. T ......................... 3 RANSPORTATION AND TORAGE 1.2. P ............................. 3 REPARATION 1.3. I ............................. 3 NSTALLATION 1.4. O ..............................4 PERATION 1.5. S ..............................4 TANDARDS 2. INSTALLATION AND OPERATION ....................5 2.1.
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1.1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact. The UPS must be stored in the room where it is ventilated and dry.
1.4. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts. Please keep the original package in a safe place for future use. 2.2. Rear Panel View Diagram 1: 6KR(L)/10KR(L) rear panel I Diagram 2: Input/Output terminal (without parallel function)
Page 7
Diagram 6: 6KR/10KR battery pack rear panel 1. RS-232 communication port 2. USB communication port 3. Emergency power off function connector (EPO connector) 4. Share current port (only available for parallel model) 5. Parallel port (only available for parallel model) 6.
Input Line Output Neutral Ground Terminal Block wiring diagram for 6KR(L)/10KR(L) NOTE 1: Make sure that the wires are connected tightly with the terminals. NOTE 2: There are two kinds of outputs: output terminal/outlets and programmable terminal. Please connect non-critical devices to the programmable terminal and critical devices to the output terminal/outlets.
Warning: (Only for standard model) ● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection. ● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery.
6) Refer to the following wiring diagram: Wiring diagram of parallel system for Rack models Parallel communication port connection Share current cable connection Diagram 2 Diagram 1: Power cable connection 2.5. Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. Install CD or visit the website http://www.power-software-download.com for the latest software version.
3. Operations 3.1. Button Operation Button Function Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. ON/Enter Button Enter Key: Press this button to confirm the selection in setting menu. Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS. OFF/ESC Button Esc key: Press this button to return to last menu in setting menu.
Page 12
Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates that the UPS alarm is disabled.
3.3. Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second Low battery Battery unconnected Over charge EPO enable Fan failure/Over temperature Beeping once every second Charger failure...
Page 14
3. Connect devices to UPS After the UPS is turned on, you can connect devices to the UPS. 1) Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load level.
Page 15
7. Turn off the UPS with utility power supply in AC mode 1) Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will beep once. The UPS will turn into Bypass mode. NOTE 1: If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to output sockets and terminal even though you have turned off the UPS (inverter).
3.5. Parallel Operation 1. Parallel system connection 1) Make sure all of the UPSs are parallel models, and follow the wiring refer to section 2-3. Turn off the input and output breakers of each UPS, and turn off the battery breaker if the UPS is long-run model.
3.6. Abbreviation Meaning in LCD Display Abbreviation Display content Meaning Enable Disable Auto Battery Normal mode (not CVCF mode) CVCF mode Subtract Not allowed Allow Reserved 3.7. LCD Setting There are three parameters to set up the UPS. Refer to following diagram. Parameter 1: It’s for program alternatives.
Page 18
Description Battery Code Bypass CVCF Battery Test Shutdown point for programmable output Hot standby function enable/disable Battery voltage adjustment Charger voltage adjustment Output voltage adjustment *Y means that this program can be set in this mode. **Programmable output setting is not supported by Rack models. 01: Output voltage Interface Setting...
Page 19
04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range is from 46.0Hz to 49.0Hz. 60 Hz system: Setting range is from 56.0Hz to 59.0Hz. The default value is 46.0Hz/56.0Hz. Parameter 3: Set the acceptable high frequency for bypass.
Page 20
09: Battery backup time setting Interface Setting Parameter 3: 000~999: Set the maximum backup time from 0min to 999min. UPS will shut down to protect battery after backup time arrives. The default value is 990min. DIS: Disable battery discharge protection and backup time will depend on battery capacity.
13: Battery voltage adjustment Interface Setting Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure. Parameter 3: the voltage range is from 0V to 5.7V, the default value is 0V. 14: Charger voltage adjustment Interface Setting Parameter 2: you may choose Add or Sub to adjust charger voltage Parameter 3: the voltage range is from 0V to 9.9V, the default value...
Page 22
Operating mode/status CVCF mode Description When input frequency is within 46 to 64Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode. LCD display Battery mode Description When the input voltage is beyond the acceptable range or power failure, UPS will backup power from battery and alarm will beep every 4 seconds.
3.9. Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure None Negative power fault None Bus over None Battery SCR short circuited None Bus under None Inverter relay short circuited None Bus unbalance None Battery voltage loss Bus short circuited None...
4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm in the front The AC input power is not Check if input cable firmly display panel even though the mains is connected well.
5. Storage and Maintenance 5.1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months...
6. Specifications MODEL LA-ON-6K-RACK LA-ON-10K-RACK 6000 VA / 4800 W 10000 VA / 8000 W CAPACITY* INPUT Low Line Loss 110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load Voltage Low Line Comeback Low Line Loss Voltage + 10V Range High Line Loss...