MGE UPS Systems GALAXY 6000 Specifications Manual

MGE UPS Systems GALAXY 6000 Specifications Manual

Parallel ups, 250 to 3000 kva*

Advertisement

MGE
Galaxy
6000:
TM
TM
Specification guide
__________________________________
Parallel UPS, 250 to 3000 kVA*
* Power rating for an N+1 configuration.

Advertisement

Table of Contents
loading

Summary of Contents for MGE UPS Systems GALAXY 6000

  • Page 1 Galaxy 6000: Specification guide __________________________________ Parallel UPS, 250 to 3000 kVA* * Power rating for an N+1 configuration.
  • Page 2: Table Of Contents

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration Contents 1 - UPS definition ... D-3 1.1 - Purpose ... D-3 1.2 - Brief description ... D-3 2 - Operating principle... D-4 2.1 - Normal operation ...
  • Page 3: Mge Tm Galaxy Tm 6000 : Specification Guide

    1.1 - Purpose The purpose of this specification is to define the design, manufacture and testing characteristics required in view of supplying, putting into operation and maintaining an Uninterruptible Power Supply (referred to as a UPS in the rest of this document).
  • Page 4: Operating Principle

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 2 - Operating principle The double-conversion UPS (also called on-line) shall operate as defined below. 2.1 - Normal operation (normal AC source available) The rectifier supplies the inverter with DC current while the charger simultaneously float charges the battery.
  • Page 5: Ups Maintenance

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 2.6 - UPS maintenance For maintenance purposes, all electronic components shall be accessible from the front of the UPS. In addition, a manually operated mechanical bypass system shall be: …………………………………………………………………………………………………………………………………..
  • Page 6: Limitation Of Harmonics Upstream Of The Ups

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 3.5 - Limitation of harmonics upstream of the UPS The UPS system shall not draw a level of harmonic currents that could disturb the upstream AC system, i.e. it shall comply with the stipulations of guide IEC 61000-3-4.
  • Page 7: Batteries

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration specified by the battery supplier (0.1 x C10 for a sealed lead-acid battery). 5.1.4 - Operating mode The charger of each UPS unit shall be sized to recharge the battery rapidly: a battery with a backup time of…[5 / 10 minutes in less than 11 hours] [15 minutes in less than 13 hours] (following a discharge to Pn/2 to recover 90% of backup time).
  • Page 8: Static Bypass

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 5.3.3 - Synchronisation with bypass power ω When bypass power is within tolerances To enable transfer to bypass power (see conditions below in section 5.4 "Static-bypass"), the inverter output voltage shall be synchronised with the bypass source voltage whenever possible.
  • Page 9: System Earthing Arrangement

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 5.6 - System earthing arrangement The UPS shall be compatible with the following system earthing arrangements: ω upstream source …[ TT/ IT / TNS / TNC ]… ω...
  • Page 10: Environment Conditions

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 7 - Environment conditions 7.1 - UPS (not including battery) 7.1.1 - Operation The UPS, not including the battery, shall be capable of operating under the following environmental conditions without loss of performance: ω...
  • Page 11: Battery Management

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 9 - Battery management As the life of the batteries is very sensitive to operating conditions, the battery shall be managed in an optimum manner.
  • Page 12: User Interface And Communication

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 10 - User interface and communication 10.1 - User interface UPS operation shall be facilitated by a user interface comprising: ω...
  • Page 13: Communication

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 10.1.3 - Status indications with mimic panel Indication of status conditions shall be distinct of the graphic display. Three LEDs on the control panel indicate the following status conditions: ω...
  • Page 14: Standards And Tests

    ω IEC 60950 / EN 60950: Safety of IT equipment, including electrical business equipment. ω IEC 61000-2-2: Compatibility levels for low-frequency conducted disturbances and signalling in public low- voltage power supply systems. ω IEC 61000-4: EMC - Electrical fast transient/burst immunity.
  • Page 15: Services

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 14 - Services 14.1 - Maintenance The supplier shall propose contracts covering four levels of maintenance. ω Level one: simple checks and settings, procedures accessible without any dismounting and involving no risk. ω...
  • Page 16: Electrical Diagram

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration 17 - Electrical diagram Normal AC input Battery UPS 1 P1 (kVA) Fig. 1. Two parallel-connected UPS units, with or without redundancy. Normal AC input UPS1...
  • Page 17: Apc By Schneider Electric Edition - 03/2009 Spec

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration Bypass Normal Normal Normal AC input AC input AC input AC input Centralized bypass Load Fig. 3. UPS system with centralized bypass (up to six units). APC By Schneider Electric Edition - 03/2009 Spec.
  • Page 18: Appendix. Comparison Table

    Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration Appendix. Comparison table Type of UPS Total rated power (kVA) at PF 0.8 Manufacturer Range of products Operating mode (IEC 62040-2) Parallel connection ≤...
  • Page 19 Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration Inverter Three-phase output voltage with neutral adjustable Steady-state conditions Voltage transients Output voltage distortion at Pn Output frequency Variation in output frequency adjustable Frequency synchronisation with an external source...
  • Page 20 Galaxy 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration Communication Programmable relay card EPO terminal block 3 slots for communication cards Options Ethernet SNMP card RS485 JBus/ModBus card RS232 U-Talk card XML-Web card Supervision software Administration software...

Table of Contents