OUTDOOR POWER FACTOR CORRECTION FAULT
Start
Check the outdoor wiring connections
for both the reactor (choke) line and
power factor correction capacitor
Any damage or
short circuit?
N
Remove power factor
correction capacitor
(CBB65) and check for
open or shorted condition
between terminals.
Is resistances
near zero?
N
Disconnect the reactor (choke)
terminals and measure
resistances between both using
ohm gauge.
Is component
damage or
short-circuited?
N
Replace outdoor
control
End
Y
Replace damage
component
If capacitor is
Y
Restart unit
short-circuited,
then replace
Replace
Y
reactor
(choke)
FIGURE 88
Page 79
APPLICABLE UNIT SIZE(S): All
APPLICABLE ERROR CODE(S): HC
Is fault corrected?
Is fault corrected?
Restart
Is fault corrected?
unit
N
Y
N
Y
N
Y
Corp. 1244-L9