Grade B Central Station And Grade A Police Connect - DSC Maxsys PC4020 System Manual

Hide thumbs Also See for Maxsys PC4020:
Table of Contents

Advertisement

UL LISTED COMMERCIAL AND
RESIDENTIAL INSTALLATIONS
The installation requirements listed below must be met for
the following grades of service.
Grade A
Local
The installation must have a bell UL Listed for mecantile
local alarms (AMSECO MBL10B) with Model AB-12 bell
housing.
The digital communicator must be enabled.
The control panel must be in the PC4004C Attack
Resistant Enclosure.
Grade B Central Station and
Grade A Police Connect
The installation must have a bell UL Listed for mecantile
local alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the PC4004C Attack
Resistant Enclosure.
Grade C
Central Station
The digital communicator must be enabled.
The control panel must be in the PC4004C Attack
Resistant Enclosure.
All Commercial Installations
• The entry delay must not exceed 60 seconds
• The exit delay must not exceed 60 seconds.
• The minimum bell cutoff time is 15 minutes.
Residential Installations
• The entry delay must not exceed 45 seconds
• The exit delay must not exceed 60 seconds.
• The minimum bell cutoff time is 4 minutes.
Programming
The notes in the programming sections describing the
system configurations for UL Listed installations must be
implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected
area is to be under the responsibility of one ownership
and management (i.e. one business under one name).
This may be a group of buildings attached or unattached
with different addresses but under the responsibility of
someone having mutual interest. The person of mutual
interest is not the alarm installing company.
Bell Location
The alarm sounding device (bell) must be located where it
can be heard by the person or persons responsible for
maintaining the security system during the daily arming
cycle.
Protection of the Control Unit
The local control and the local power supply must be
protected by one of the following ways:
• The control unit and audible alarm device must be in a
protected area which is armed 24 hours a day.
• Each partition shall arm the area protecting the control
unit and the audible alarm device power supply. This
may require duplicate protection armed by each
partition. Access to this protected area, without causing
an alarm, will require that all partitions be disarmed.
In all cases described above, the protected area for the
control unit must be programmed as not bypassable.
Casual Users
The installer should caution the user(s) to not give system
information to casual users (e.g. codes, bypass methods,
etc. to baby-sitters or service people). Only the One-Time
Use codes should be given to casual users.
User Information
The installer should advise the users and note in the user
instruction manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
26