Locating Your Fireplace; Clearance To Combustibles; Mantels - Majestic fireplaces 360DVS2 Homeowner's Installation And Operating Manual

Multisided top/rear vent convertible direct vent
Table of Contents

Advertisement

Locating Your Fireplace

X
Y
A
Y
LU584-2
Fig. 3 Locating your gas fireplace
360DVS
A Wall Location (Fig. 3)
Y (Minimum distance between a glass panel and a
locate fireplace
parallel wall) = 3' (914mm)
Z (Minimum distance between edge of a glass panel
and an adjacent wall) = 3" (76mm)
B Island Location (Fig. 3)
X (Maximum length of horizontal venting) = 20' (6.1m)
Refer to the venting section in this manual for specific dimen-
sions.

Clearance to Combustibles

Top of unit to ceiling ................................. 36" (914 mm)
Front of unit to combustibles ................... 36" (914 mm)
Appliance
Top .........................................0" (0 mm) to standoff
Bottom ..................................................... 0" (0 mm)
Vent End ....................... 1/2" (13 mm) to rear panel
Nonvent End (DVS2) .............................. 0" (0 mm)
Venting
Concentric sections of DV Vent:
Top, bottom & sides .............................. 1" (25 mm)
Nonconcentric sections of DV Vent:
Side and bottom .................................... 1" (25 mm)
Top ........................................................ 2" (51 mm)

Mantels

The height at which a combustible mantel is fitted
above the fireplace is dependent on the depth of the
mantel. This also applies to the distance between the
mantel leg (if so fitted) and the fireplace. For correct
mounting height and width, refer to Fig. 4a and 4b and
the Mantel Chart below.
The fitting of a bay window trim kit does not affect the
distances and reference points referred to in the dia-
gram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent dis-
coloration.
10006326
X
X
B
Y
A
Z
LU584-2
360DVS Series Direct Vent Fireplaces
A
B
C
D
Bottom of Door Trim
Mantel Chart
Mantel Shelf
CFM146
DV Mantel Chart
Ref.
or Breast Plate
7/5/01 sta
V
10" (254 mm)
W
8" (203 mm)
X
6" (152 mm)
Y
4" (102 mm)
Z
2" (51 mm)
Fig. 4a Combustible mantel minimum installation.
Top View
Mantel Leg
CFM197
Front View
Side of Combustion
CFM197
Chamber
Mantel Corner Leg Chart
04/16/02 sta
Mantel
Ref.
Leg Depth
CFM170
F
10" (254 mm)
DV Builder Front
View
G
8" (203 mm)
H
6" (152 mm)
I
4" (102 mm)
J
2" (51 mm)
Fig. 4b Combustible mantel leg minimum installation.
V
W
X
Y
Z
E
Fireplace
Louvre Assembly
Top
Top of Combustion
Chamber
CFM146
Mantel from Top
Ref.
of Comb. Chamber
A
19" (483 mm)
B
17" (432 mm)
C
15" (381 mm)
D
13" (330 mm)
E
11" (297 mm)
J
I
H
G
F
K
L
M
N
O
Mantel
Leg
CFM170
Mantel Leg From Side
Ref.
of Comb. Opening
K
11¹⁄₂" (292 mm)
L
9¹⁄₂" (241 mm)
M
7¹⁄₂" (191 mm)
N
5¹⁄₂" (140 mm)
O
3¹⁄₂" (89 mm)
9