1

Determine water heater location

Installation must comply with:
• Local, state, provincial, and national codes, laws,
regulations, and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• National Electrical Code.
• For Canada only: B149.1 Installation Code, CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
The Shield water heater gas manifold and
NOTICE
controls met safe lighting and other
performance under tests specified in
ANSI Z21.10.3 – latest edition.
Before locating the water heater, check:
1.
Check for nearby connection to:
• Water piping
• Venting connections
• Gas supply piping
• Electrical power
2.
Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the
appliance. Under no circumstances is the manufacturer
to be held responsible for water damage in connection
with this appliance, or any of its components.
3.
Check area around the water heater.
combustible materials, gasoline and other flammable
liquids.
Failure to keep water heater area clear and
WARNING
free of combustible materials, gasoline,
and other flammable liquids and vapors
can result in severe personal injury, death,
or substantial property damage.
4. The Shield water heater must be installed so that gas
control system components are protected from dripping
or spraying water or rain during operation or service.
8
WARNING
WARNING

Closet and alcove installations

A closet is any room the water heater is installed in which is
less than 455 cubic feet for SNR150-100 and SNR200-100
models and 671 cubic feet for the SNA285-125 through
SNA500-125 models.
An alcove is any room which meets the criteria for a closet
with the exception that it does not have a door.
Remove any
Example: Room dimensions = 6 feet long, 6 feet wide, and
9 foot ceiling = 6 x 6 x 9 = 324 cubic feet. This would be
considered a closet for a Shield Water Heater.
WARNING

Provide clearances:

Clearances from combustible materials
1. Hot water pipes—at least 1" from combustible materials.
2. Vent pipe – at least 1" from combustible materials.
3. See FIG.'s 1-1 and 1-2 on page 9 for other clearance
minimums.
Clearances for service access
1.
See FIG.'s 1-1 and 1-2 on page 9 for recommended
service clearances. If you do not provide the minimum
clearances shown, it may not be possible to service the
water heater without removing it from the space.
Installation & Service Manual
TM
This appliance is certified as an indoor
appliance. Do not install the appliance
outdoors or locate where the appliance will
be exposed to freezing temperatures or to
temperatures that exceed 100°F.
Failure to install the appliance indoors
could result in severe personal injury,
death, or substantial property damage.
This appliance requires a special venting
system.
The vent connection to the
appliance must be made with the CPVC
pipe section installed in the appliance. The
field provided vent fittings must be
cemented to the CPVC pipe section. Use
only the vent materials, primer and cement
specified in this manual to make the vent
connections.
Failure to follow this
warning could result in fire, personal
injury, or death.
For closet and alcove installations as
shown in FIG.'s 1-1 and 1-2, CPVC vent
material must be used inside the structure.
The ventilating air openings shown in
FIG.'s 1-1 and 1-2 are required for this
arrangement.
Failure to follow this
warning could result in fire, personal
injury, or death.