B-7

AUXILIARY POWER:

Start the engine and set the IDLER control switch to
the desired operating mode. Full power is available
regardless of the welding control settings providing no
welding current is being drawn.
The auxiliary power of the RANGER 305D consists of
two 20 Amp-120 VAC (5-20R) duplex receptacles and
one 50 Amp 120/240 VAC (14-50R) receptacle. The
240 VAC receptacle can be split for single phase 120
VAC operation.
The auxiliary power capacity is 10,000 watts Peak,
9500 Watts continuous of 60 Hz, single phase power.
The auxiliary power capacity rating in watts is equiva-
lent to volt-amperes at unity power factor. The max
permissible current of the 240 VAC output is 44 Amps.
The 240 VAC output can be split to provide two sepa-
rate 120 VAC outputs with a max permissible current
of 44 Amps per output to two separate 120 VAC
branch circuits (these circuits cannot be paralleled).
Output voltage is within ± 10% at all loads up to rated
capacity.
The 120 V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs. The current
rating of any plug used with the system must be at
least equal to the current capacity of the associated
receptacle.
Welding
Output-Amps
0
100
150
200
250
300
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 44A per 120 VAC branch circuit when splitting the 240 VAC output.
(Use the shortest length extension cord possible sized per the following table.)
Current
Voltage
Load
(Amps)
Volts
(Watts)
15
120
1800
20
120
2400
15
240
3600
20
240
4800
44
240
9500
OPERATION
RANGER 305D Simultaneous Welding and Power Loads
Permissible Power-Watts
(Unity Power Factor)
10000
7500
5800
4500
2800
700
RANGER 305D Extension Cord Length Recommendations
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
30
(9)
60
(18)
75
(23)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
RANGER 305D
NOTE: The 240 V receptacle has two circuits, each of
which measure 120 V to neutral but are of opposite
polarities and cannot be paralleled.

Simultaneous Welding and Auxiliary Power Loads

The above auxiliary power ratings are with no welding
load. Simultaneous welding and power loads are
specified in the following table. The permissible cur-
rents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the
same time).
Permissible Auxiliary
Current in -Amps
@ 240 VAC
10 AWG
8 AWG
75
(23)
125
(38)
50
(15)
88
(27)
150
(46)
225
(69)
100
(30)
175
(53)
50
(15)
90
(27)
44
31
24
19
12
3
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
225
(69)
350
(107)
600
(183)
275
(84)
450
(137)
150
(46)
225
(69)
B-7