Download Print this page

Liebert 1800 Specifications

Process fluid chiller designed for varian clinac 18r, 1800, 2100c/d & 2300c/d

Advertisement

Quick Links

Keeping Business in Business
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• UL/CSA listing on standard models.
• ISO 9001 certified company.
CLINAC 18R, 1800, 2100C/D, 2300C/D Specifications
Fluid Specified
Heat Dissipation—BTUH (kW)
Fluid Temperature Range—°F (°C)
Fluid Flow Rate—GPM (l/m)
Fluid Pressure Drop—PSI (kPa)
Note: Performance is based on 95°F condenser ambient.
Model Number
Fluid Circulated
Net Cooling Capacity—BTUH (kW)
Leaving Fluid Temperature—°F (°C)
Fluid Flow Rate—GPM (l/m)
CLINAC Pressure Drop—PSI (kPa)
Chiller Pressure Drop—PSI (kPa)
Pump Total Head—PSI (kPa)
Head Available for Piping Circuit—PSI (kPa)
Pump HP (kW)
Process Fluid Chiller Designed for
Varian CLINAC 18R, 1800, 2100C/D & 2300C/D
Water
85,350 (30)
50-75 (10-25)
4 (15.2) @ 60°F (15.6°C)
6 (41.4)
Process Fluid Chiller Specifications
PS096A
Water
86,000 (25.2)
51 (10.6)
4.3 (16.2)
6 (41.4)
4.1 (28.2)
62.3 (428.6)
52.2 (360)
3 (2.2)
Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/D
PS096A
PS096A
Ethylene Glycol
Propylene Glycol
86,000 (25.2)
86,000 (25.2)
55 (12.8)
58 (14.4)
4.3 (16.2)
4.3 (16.2)
6 (41.4)
6 (41.4)
5.5 (37.8)
6.3 (43.2)
62.3 (428.6)
62.3 (428.6)
50.8 (350)
50 (345)
3 (2.2)
3 (2.2)
1

Advertisement

loading

Summary of Contents for Liebert 1800

  • Page 1 Chiller Pressure Drop—PSI (kPa) Pump Total Head—PSI (kPa) Head Available for Piping Circuit—PSI (kPa) Pump HP (kW) Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/D Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/D Water...
  • Page 2 35028 Piove Di Sacco Phone: 800.877.9222 Italy Fax: 614.841.6022 Phone: 39.049.9719.111 Fax: 39.049.5841257 Liebert Web Site—http:www.liebert.com SL-16563 (07/00) Process Fluid Chiller Designed for Varian CLINAC 18R, 1800, 2100C/D & 2300C/D C-Depth Weight in. (mm) lbs. (kg) 38.5 (978) 5.5 (140) 750 (340) 38.5 (978)

This manual is also suitable for:

2100c/d2300c/dClinac 18rPs096aPs120a