Liebert UPS User Manual page 34

6 & 10 kva 208v & 240v
Table of Contents

Advertisement

MODEL NUMBER
MODEL RATING VA/W (max)
DIMENSIONS: mm (in)
Unit
W x D x H
Shipping
W x D x H
WEIGHT: kg (lbs)
Unit
Shipping
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 90% Loading
90% - 70% Loading
70% - 30% Loading
30% - 0% Loading
Frequency
Input connection
OUTPUT AC PARAMETERS
Output connection
Voltage
Frequency
Waveform
Main Mode Overload
BATTERY PARAMETERS
Type
Qty. x Voltage x Rating
Back-up Time
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
EMI/EMC
Immunity
SPECIFICATIONS
GXT6000T-208X
5400 / 3780
260 x 555 x 803
(10.3 x 21.9 x 31.6)
400 x 850 x 1065
(15.8 x 33.5 x 41.9)
142 (313)
173 (381)
208 VAC nominal; variable based upon output load
186 VAC to 280 VAC; ±5.0 VAC
159 VAC to 280 VAC; ±5.0 VAC
139 VAC to 280 VAC; ±5.0 VAC
119 VAC to 280 VAC; ±5.0 VAC
46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing
200% for 8 cycles; 130% for 10 seconds, then transfer to
Valve-regulated, nonspillable, lead acid
20 x 12V x 7.0 Ah
7 min. minimum
0° C to +40° C (+32° F to +104° F)
-15° C to +50° C (+5° F to +122 °F)
Up to 3000 m (10,000 ft.) at 40° C without derating
15,000 m (50,000 ft.) maximum
<55 dB "A" at 1 meter
34
Hardwire terminal block
Hardwire terminal block
208/120 VAC; ±7%
50 Hz or 60 Hz; auto sensing
Sinewave
bypass
0% to 95%, non-condensing
UL1778, Listed
FCC Part 15, Class A
IEEE C62.41:1991
GXT10000T-208X
9000 / 6300
340 x 650 x 960
(13.4 x 25.6 x 37.8)
510 x 840 x 1235
(20.1 x 33.1 x 48.6)
247 (544)
287 (633)
40 x 12V x 7.0 Ah
10 min. minimum
<65 dB "A" at 1 meter

Hide quick links: