Communications Interface Port; Pin Assignment - Liebert UPS User Manual

6 & 10 kva 208v & 240v
Table of Contents

Advertisement

COMMUNICATIONS INTERFACE PORT

The UPStation GXT UPS contains a standard DB-9 socket located on the rear of
the UPS unit. Several signals are provided on this port and are assigned as
follows:
PIN
ASSIGNMENT DESCRIPTION
1
Low Battery (open collector)
2
UPS TxD (typical RS-232 levels)
3
UPS RxD (typical RS-232 levels)
4
Remote Shutdown (5-12V); battery operation
5
Common
6
Remote Shutdown (short to pin 5); any mode
7
Low Battery (open emitter)
8
Utility Fail (open emitter)
9
Utility Fail (open collector)

PIN ASSIGNMENT

*Maximum voltage and current on pins 1,7,8,9 is 80V DC; 10.0 mA.
CAUTION:
TO MAINTAIN SAFETY (SELV-Safety Extra Low Voltage)
BARRIERS AND FOR ELECTROMAGNETIC COMPATIBILITY, SIGNAL
CABLES SHOULD BE SEGREGATED AND RUN SEPARATE FROM ALL
OTHER POWER CABLES, BY 1inch (25mm) WHERE APPLICABLE.
COLLECTOR TO EMITTER*
28