GXT6000T / 10000T - 208 UPS ONLY
Models whose part number ends with a "208" are NOT fitted with an isolating
output transformer and are NOT separately derived sources under the NEC. The
output L1 terminal is connected to the input L1 terminal and must not be
connected to ground at the UPS (see NEC 250-5d, 250-26, 250.91, 250.92).
CONNECTION
INPUT
OUTPUT
BATTERY
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
CONNECTION
INPUT
OUTPUT
BATTERY
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
INPUT
UTILITY
L
1
INPUT TO UPS
NOTE 1
GXT6000T-208 CONNECTIONS
CURRENT
RATING
28 AMPS
26 AMPS
23 AMPS
GXT10000T-208 CONNECTIONS
CURRENT
RATING
45 AMPS
43 AMPS
37 AMPS
OUTPUT
NOTE 4
L
2
OUTPUT TO LOAD
Recommended
Wire Size
8 AWG (10 mm²)
8 AWG (10 mm²)
8 AWG (10 mm²)
Recommended
Wire Size
6AWG (16 mm²)
6AWG (16 mm²)
6AWG (16 mm²)
L
L
1
2
NOTE 2
10
Recommended External
Overcurrent Protection
40 AMPS
Recommended External
Overcurrent Protection
60 AMPS
OPTIONAL
BATTERY
+
OPTIONAL
BATTERIES
NOTE 3
-