Refrigerant Piping - Daikin FTXS50FV1B Installation Manual

R410a split series
Hide thumbs Also See for FTXS50FV1B:
Table of Contents

Advertisement

2.

Refrigerant piping.

CAUTION
1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
Flare nut
Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.
2-1. Caution on Piping Handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender
for bending.
2-2. Selection of Copper and Heat Insulation materials
• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-
sions as below.
Gas side
50/60 class
O.D. 12.7mm
Minimum bend radius
40mm or more
Thickness 0.8mm
Thickness 1.0mm
(C1220T-O)
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
■English
[Apply oil]
Do not apply refrigeration
oil to the outer surface.
Gas side
1/2 inch
49.5-60.3N m
(505-615kgf cm)
Valve cap tightening torque
Liquid side
Gas pipe thermal insulation
71 class
50/60/71 class
O.D. 15.9mm
O.D. 6.4mm
I.D. 14-16mm I.D. 16-20mm
50mm or more
30mm or more
Thickness 0.8mm
(C1220T-O)
(C1220T-O)
Apply refrigeration oil to
the inner surface of the
flare.
Spanner
Piping union
Flare nut tightening torque
Liquid side
5/8 inch
61.8-75.4N m
14.2-17.2N m
(630-770kgf cm)
(144-175kgf cm)
Liquid pipe
thermal insulation
50/60 class
71 class
50/60/71 class
I.D. 8-10mm
Thickness 10mm Min.
[Tighten]
Torque wrench
Flare nut
1/4 inch
Be sure to
place a cap.
Rain
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Inter-unit wiring
Gas pipe
Gas pipe
insulation
Finishing tape
Wall
Liquid pipe
Liquid pipe
insulation
Drain hose
10