A I R C O N D T I O N E R S XC16 ELITE Series ® R-410A - Two-Stage Compressor E N G I N E E R I N G D A T A Bulletin No. 210465 October 2010 Supersedes September 2010 SEER up to 17.20...
Page 2
Fan guard constructed of corrosion-resistant PVC which is based on AHRI Standard 210/240-2008. (polyvinyl chloride) coated steel. Sound rated in Lennox reverberant sound test room Fan service access accomplished by removal of fan in accordance with test conditions included in AHRI guard.
Page 3
FEATURES REFRIGERATION SYSTEM (CONTINUED) COMPRESSOR Copeland Scroll Ultra Tech™ Two-Stage Compressor High Pressure Switch Compressor features high Shuts off unit if abnormal operating conditions cause the efficiency with uniform discharge pressure to rise above setting. suction flow, constant Protects compressor from excessive condensing discharge flow and high pressure.
Page 4
Thermostat OPTIONS Thermostat not furnished with unit. See Thermostat Crankcase Heater (Optional for 024-036 models) bulletins in Controls Section and Lennox Price Book. Crankcase heater prevents migration of liquid CAbinet refrigerant into compressor and ensures proper Heavy-gauge steel construction compressor lubrication.
SPECIFICATIONS General Model No. XC16-024 XC16-036 XC16-048 XC16-060 Data Nominal Tonnage Connections Liquid line (o.d.) - in. (sweat) Suction line (o.d.) - in. 1-1/8 Refrigerant R-410A charge furnished 7 lbs. 6 oz. 8 lbs. 8 oz. 11 lbs. 4 oz.
OUTDOOR SOUND DATA Octave Band Sound Power Levels dBA, re 10- Watts Sound Center Frequency - HZ Rating Unit Number Model No. 1000 2000 4000 8000 (dB) XC16-024 68.5 65.5 58.5 XC16-036 50.5 54.5 59.5 XC16-048 81.5 72.5 68.5 64.5 59.5 56.5...
Page 7
(216) (241) 8−3/4 8−1/4 (222) (210) 13−1/2 5−1/2 (343) (140) XC16-024 BASE SECTION XC16-036 TO -060 BASE SECTION Model No. in. mm in. mm XC16-024 39 991 30-1/2 775 - - - - - - - - - - - - - - - - - -...
Page 8
CBX26UH-024 37L51 XC16-060 91M02 XC16-036 CX34-42 37L51 CX34 upflow coils and all Lennox air handlers (except CB26UH “R”) are shipped with a factory installed TXV. In most cases, no change out of the valve XC16-036 CX34-43 37L51 is needed. XC16-036...
Page 9
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 10
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 11
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 12
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 13
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 14
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 15
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 16
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 17
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 18
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 19
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 20
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 21
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 22
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 23
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 24
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 25
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 26
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 28
Contact us at 1-800-4-LENNOX NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.