American power conversion smart-ups user's manual 600xl, 900xl, 2000xl.

 
Smart-UPS
Models 600XL,
900XL and 2000XL
User's
User's
User's
User's
User's
Manual
Manual
Manual
Manual
Manual
TM
®
Next page ->

Summary of Contents

  • Page 1

    Smart-UPS Models 600XL, 900XL and 2000XL User's User's User's User's User's Manual Manual Manual Manual Manual ®...

  • Page 2

    Class A prescrites dans le Règlement sur le brouillage radioélectrique édicte par le ministère dès Communications du Canada. Hiermit wird bescheinigt, dass der Smart-UPS 600XL, 900XL, 2000XL Ununterbrechbare Stromversorgungs-Gerät in Unereinstimmung mit den Bestimmungen der Vfg 1046/1984 funk-entstort ist.

  • Page 3: Table Of Contents

    1.0 Introduction ... 2 2.0 Safety!... 4 Sécurité! (Français) ... 5 Sicherheit! (Deutsch) ... 6 ¡Seguridad! (Español) ... 7 3.0 Presentation ... 8 600VA and 900VA models... 8 2000VA models ... 10 4.0 Installation ... 13 5.0 Operation ... 18 6.0 UPS monitoring ...

  • Page 4

    1.1 Overview This equipment is a high performance line interactive uninterruptible power source (UPS) designed to provide clean, reliable AC power to computer loads. The UPS's line interactive circuit topology, illustrated below, offers excellent efficiency, on-line voltage regulation and fast utility fault response. The UPS’s DC-to-AC inverter is always connected to the output and when operating on- line, a portion of the inverter circuitry is put to work “in reverse”...

  • Page 5

    1.2 SmartBoost SmartBoost allows continuous on-line operation during extended brownouts or low line voltage conditions. The UPS compensates for the reduced line voltage by boosting the load voltage to a value 12% above the input. Reliability is enhanced because the limited battery capacity is saved for complete utility failures.

  • Page 6

    CAUTION ! To reduce the risk of electric shock, disconnect the Uninterruptible Power Source from the mains before installing computer interface signal cable (when used). Reconnect the power cord only after all signalling interconnections have been made. Connect the Uninterruptible Power Source to a two-pole, three-wire grounding mains receptacle.

  • Page 7

    ATTENTION! Pour réduire le risque d’électrocution, débranchez la prise principale de la source d’alimentation permanente (Uninterruptible Power Source), avant d’installer le câble d’interface allant à l’ordinateur (si utilisé). Ne rebranchez le bloc d’alimentation qu’après avoir effectué toutes les connections. Branchez la source d’alimentation permanente (UPS) dans une prise de courant à 3 dérivations (deux pôles et la terre).

  • Page 8

    VORSICHT! Um die Gefahr eines elektrischen Schlages auf ein Minimum zu reduzieren, die unterbrechungsfreie Stromversorgung vom Stromnetz trennen, bevor ggf. ein Com- puter-Schnittstellensignalkabel angeschlossen wird. Das Netzkabel erst nach Herstellung aller Signalverbindungen wieder einstecken. Die unterbrechungsfreie Stromversorgung an eine geerdete zweipolige Dreiphasen- Netzsteckdose anschließen.

  • Page 9

    ¡ATENCION! Para reducir el riesgo de descarga eléctrica, desconecte de la red la Fuente de energía ininterrumpible antes de instalar el cable de señalización de interfaz de la computadora (si se usa). Vuelva a conectar el conductor flexible de alimentación solamente una vez efectuadas todas las interconexiones de señalización.

  • Page 10: Va Models

    3.1 600VA and 900VA models - 120 Vac version Note: Use only factory supplied or authorized Battery packs. On / Test / Alarm disable pushbutton See section 5.1. Display features section 5.0. Power standby pushbutton See section 5.1. Electronics enclosure Battery pack Front view...

  • Page 11

    3.2 600VA and 900VA models - 220/230/240 Vac version Note: Use only factory supplied or authorized Battery packs. On / Test / Alarm disable pushbutton See section 5.1. Display features section 5.0. Power standby pushbutton See section 5.1. Electronics enclosure Battery pack Front view...

  • Page 12

    3.3 2000VA model - 120 Vac version Note: 2000V A model Battery pack not shown. Use only factory supplied or authorized Battery packs. 15Amp circuit On / Test / Alarm disable pushbutton See section 5.1. Display features section 5.0. Power standby pushbutton See section...

  • Page 13: Installation

    3.4 2000VA model - 120 Vac version options The -1, -2 and -4 wiring device options for the 120 Vac version 2000VA model UPS are shown below for reference. These options allow simple plug-in installation of the UPS where special service or load wiring devices are used. Note: There is no Option -3.

  • Page 14

    3.5 2000VA model - 220/230/240 Vac version Note: 2000V A model Battery pack not shown. Use only factory supplied or authorized Battery packs. On / Test / Alarm disable pushbutton See section 5.1. Display features section 5.0. Power standby pushbutton See section 5.1.

  • Page 15

    4.1 Receiving inspection Once the UPS has been removed from its shipping container, it should be inspected for damage that may have occurred while in transit. Immediately notify the carrier and place of purchase if any damage is found. The packing materials are made from recyclable materials and should be saved for reuse or disposed of properly.

  • Page 16

    4.4 Connect battery pack Follow the instructions listed below to install and lock the battery pack coupler. Note: Use only factory supplied or authorized battery packs! 4.4.1 Remove the battery coupler clamp from the Electronics enclosure. 4.4.2 Turn the battery coupler clamp and refasten loosely at one side. 4.4.3 Mate the battery pack coupler to the electronics enclosure.

  • Page 17

    4.4 Connect battery pack - continued Note: Leave adequate space for cooling. Typical 2000VA model multiple Battery pack installation - 120 Vac version shown. Note: The number of 2000V A model Battery packs that may be connected is limited only by the recharge time desired - see section 9.9.

  • Page 18: Operation

    4.5 Connect UPS to service and enable - continued 220/230/240 Vac versions The 600VA and 900VA UPS is not furnished with an input line cord. Instead, two output cords are supplied. However, in most installations it will not be necessary to purchase a UPS input power cord.

  • Page 19

    4.6 Plug loads into UPS Plug all loads to be protected into the UPS. Do not exceed the UPS's capacity as given in section 9.0. Once switched on, the UPS will monitor and display the magnitude of the applied load. Note: Do not plug laser printers into this UPS.

  • Page 20: Operation

    5.1 Display features On Battery indicator On Line indicator Power bar graph Power standby pushbutton 5.1.1 On / Test / Alarm disable pushbutton The On / Test / Alarm disable pushbutton is used to control activation of the UPS and to energize the load.

  • Page 21

    5.2 Battery capacity bar graph The battery capacity bar graph continuously displays the state of battery charge. In the above example, the display shows that 100% of rated battery capacity is available. Where power quality is fair, the UPS will be able to maintain the battery at 100% of rated capacity.

  • Page 22

    5.4 Line voltage bar graph The line voltage bar graph displays the UPS's input voltage in discrete steps. Line voltage is displayed when the I/Test pushbutton is pressed and held. The example above shows that the UPS's input line voltage is between 116 and 123 Vac (120 Vac version UPS, see table for values for other versions).

  • Page 23

    5.5.3 Replace battery In the event the UPS's battery fails a battery test, the UPS will emit "chirps" for a period of 1 minute. If the UPS is left operating while in this condition, the UPS will emits chirps once every 5 hours until a successful battery test is completed. 5.5.4 Overload The UPS will emit a loud, sustained tone when overloaded.

  • Page 24

    5.6 Option switches - continued 5.6.2 Option switch 2 Option switch 2 controls different functions depending upon the UPS version type. 120 Vac version The UPS's factory set input voltage limits for on-line and SmartBoost operation are given in section 9.0 and are centered on the nominal input voltage of 120 Vac. When Option switch 2 is set to the on ( I ) position, the upper and lower transfer voltages are lowered by 4% and are centered on a nominal input of 115 Vac.

  • Page 25

    5.7 Extended capabilities The following sections briefly describe the UPS’s extended capabilities. These advanced functions are accessed by a computer running optional PowerDoctor or PowerChute plus UPS monitoring software. See the UPS monitoring software literature for more informa- tion on the application of these functions. Note: The extended capabilities of the UPS and operation of UPS monitoring software may be altered or amended without notice.

  • Page 26: Ups Monitoring

    5.7 Extended capabilities - continued Output voltage, internal temperature, battery voltage, battery capacity - The UPS continuously monitors the rms output voltage, internal temperature in degrees Celsius, battery voltage, and the remaining battery capacity as a percentage of the fully charged condition.

  • Page 27

    5.7 Extended capabilities - continued output voltage may be set to a nominal 220, 225, 230 or 240 Vac. The UPS’s default setting is 225 Vac. Utility failure sensitivity - The UPS’s sensitivity to line voltage distortions may be customized to allow use of the UPS in “noisy” electrical environments or with fuel powered generators.

  • Page 28: Ups Monitoring

    6.1 Overview A UPS system alone provides excellent protection from brief power problems. However, during an extended power outage an unattended computer system will eventually shut down due to battery capacity exhaustion. To prevent data corruption when the UPS shuts down, the computer must be informed by the UPS of impending shut down and take appropriate file-saving measures.

  • Page 29

    6.4 Computer interface port The computer interface port is diagramed below for your reference. Those with technical abilities wishing to use this port in a special application should be aware of the following limitations and capabilities of the interface. Outputs at pins 3, 5 and 6 are actually open collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc.

  • Page 30

    CAUTION ! This Uninterruptible Power Source contains potentially hazardous voltages. Do not attempt to disassemble the unit. The unit contains no user serviceable parts. Repairs are performed only by factory trained service personnel. This Uninterruptible Power Source uses batteries. The batteries will eventually become too weak to provide rated autonomous operation.

  • Page 31

    FRANÇAIS ATTENTION! Cette source d’alimentation permanente (UPS) contient des circuits haute tension présentant un danger. Ne jamais essayer de le démonter. Il n’y a aucun composant qui puisse être réparé par l’utilisateur. Toutes les réparations doivent être effectuées par du personnel qualifié...

  • Page 32

    DEUTSCH VORSICHT! Im Inneren dieser unterbrechungsfreien Stromversorgung herrschen potentiell gefährliche Spannungen. Nicht versuchen, das Gerät zu öffnen. Es enthält keine vom Benutzer reparierbaren Teile. Reparaturen dürfen nur von ausgebildetem Kundendienstpersonal durchgeführt werden. Diese unterbrechungsfreie Stromversorgung enthält Batterien, die nach einer bestimmten Zeit so schwach werden, daß...

  • Page 33

    ESPAÑOL ¡CUIDADO! Esta Fuente de energía ininterrumpible contiene niveles de voltaje peligrosos en potencia. No intente desarmar la unidad, pues no contiene piezas que puedan ser reparadas por el usuario. Las reparaciones deben efectuarse únicamente por parte del personal de mantenimiento capacitado en la fábrica. Esta Fuente de energía ininterrumpible contiene baterías.

  • Page 34

    7.1 Troubleshooting chart PROBLEM POSSIBLE CAUSE 1. UPS Enable switch is in the off position or front panel switch not pressed. 2. UPS’s input circuit breaker is UPS will not turn on. tripped (button is extended). 3. Very low utility voltage or dead outlet.

  • Page 35

    7.2 Battery replacement check You can expect to receive 3 to 6 years of service life from the UPS's Battery packs when installed in a cool, dry location. Battery life is shortened when operated in an environ- ment where the ambient temperature is normally above 30°C (86°F). The UPS automatically performs a battery test upon start up and, if left operating, every 14 days thereafter.

  • Page 36

    7.3 Obtaining Service The troubleshooting chart in section 7.1 covers most of the difficulties that a user may encounter under conditions other than a failure of the UPS itself. For problems not covered in the chart, the procedures outlined below should be followed. If your UPS should require service: See the troubleshooting chart and eliminate the obvious.

  • Page 37

    8.1 Storage conditions The UPS should be covered and stored upright in a cool dry location. The UPS should be stored with its Battery packs in a fully charged state. That is, the indicated battery capacity should be 100% before the UPS is switched off for storage. Once charged, disconnect the Battery packs from each other and from the UPS.

  • Page 38: Specifications

    Note: Where specifications ratings differ, values for the 220/230/240 Vac versions are given in [ ] brackets. 9.1 Input Nominal input voltage: single phase, 120 Vac, [220/230/240 Vac]. Nominal input frequency: 50 or 60 Hz, internally selected by microprocessor. Input protection; 600VA, 900VA model: 14 Amp, [12 Amp] resettable circuit breaker. Input protection, 2000VA model: [15 Amp] resettable circuit breaker.

  • Page 39

    9.4 Noise and surge suppression Surge energy rating (one time, 10/1000 µs waveform): 480 J. Surge current capability (one time, 8/20 µs waveform): 6500 Amp peak maximum. Surge response time: 0 ns (instantaneous) normal mode, <5 ns common mode. Surge voltage let-through: <0.3%, [<2%] of applied ANSI C62.41 Category A ± 6 kV test waveform.

  • Page 40

    Page 38...

  • Page 41

    Page 39...

  • Page 42

    DECLARATION OF CONFORMITY Application of Council Directive(s): Standard(s) to which Conformity is Declared: Manufacturer's Name: Manufacturer's Address: Importer's Name: Importer's Address: Type of Equipment: Model No.: Serial Number: Year of Manufacture: I, the undersigned, hereby declare that the equipment specified above conforms to Place: Date: Page 40...

  • Page 43

    THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAM- AGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.

  • Page 44

    Entire contents copyright © 1993 American Power Conversion. All rights reserved; reproduction in whole or in part without permission is prohibited. Smart-UPS, PowerDoctor and PowerChute are registered trademarks of APC. SNMP Adapter and SmartBoost are trademarks of APC. All other trademarks are the property of their respective owners.