5 Commissioning Part I
5.6
Filling the condensate siphon
1
Fig. 5.4 Filling the condensate siphon
Danger!
Note that if the boiler is run with an empty
condensate trap there is a danger that fumes
might escape into the room and cause poison-
ing. For this reason, it is important to ensure
that the trap is topped up each time the unit is
cleaned.
• Remove the lower part (1) of the condensate siphon by
turning the bayonet catch in anticlockwise direction.
• Fill the lower part with water until about 10 mm below
the upper edge.
• Refit the lower part of the condensate siphon.
5.7
Adjusting the pumping capacity
Only in ecoTEC plus boilers:
The capacity of the two-stage pump can be adjusted to
the requirements of the heating system. If needed,
change the setting of the operating mode dependent
pump speed under the diagnostic number “d.19” (see
section 8.1.2).
5.8
Adjusting the by-pass
The appliances have an adjustable by-pass valve.
The pressure can be adjusted between 170 and
350 mbar. Approx. 250 mbar is preset (mid-position).
The pressure changes by approx. 10 mbar each time the
adjusting screw is rotated. By turning right, the pressure
increases and turning left decreases it.