Generac Power Systems Automatic Standby Generator Owner's Manual

Generac Power Systems Automatic Standby Generator Owner's Manual

8 kw to 22 kw automatic standby generator
Hide thumbs Also See for Automatic Standby Generator:

Advertisement

Owner's Manual
Automatic Standby Generator
NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS.
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT
INSTALLATION.
DEADLY EXHAUST FUMES! OUTDOOR INSTALLATION ONLY!
To locate in Spanish, go to
To locate in French, go to
Reference all appropriate documentation.
This manual should remain with the unit.
http://www.generac.com/service‐support/product‐support‐lookup
http://www.generac.com/service‐support/product‐support‐lookup
8 kW to 22 kW

Advertisement

Table of Contents
loading

Summary of Contents for Generac Power Systems Automatic Standby Generator

  • Page 1 Owner’s Manual Automatic Standby Generator 8 kW to 22 kW NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION. DEADLY EXHAUST FUMES! OUTDOOR INSTALLATION ONLY! http://www.generac.com/service‐support/product‐support‐lookup To locate in Spanish, go to http://www.generac.com/service‐support/product‐support‐lookup...
  • Page 2 AUTHORIZED SERVICE DEALER, please call this number: 1-800-333-1322 or, visit the dealer locator at: www.generac.com/Service/Dealer Locator/ WARNING! California Proposition 65 Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth defects, and other reproductive harm.
  • Page 3: Table Of Contents

    Table of Contents Frequently Asked Questions ..............iv Section 1 —...
  • Page 4: Frequently Asked Questions

    How do I size the correct gas line for my home standby generator installation? Generac is not able to size the gas line for you. However, Generac is able to give the fuel consumption and required water column which will help the gas installers to provide the correct size needed for installation.
  • Page 5 Maintenance kits and parts can be purchased from any sales or service dealer, through our part distributors (GPCs) or online at ordertree.com. Only Generac-brand maintenance parts should be used. We don’t rec- ommend and don’t have cross-reference numbers for other brands like Fram or Napa.
  • Page 6 What is an automatic standby generator? An automatic standby generator is a back-up electrical system that operates whether you are home or away. Within seconds of an outage, it automatically supplies power directly to your home’s electrical circuit breaker...
  • Page 7: Section 1 - Safety

    Section 1 INTRODUCTION: Thank you for purchasing this compact, high performance, air-cooled, engine-driven stationary automatic standby generator set. Every effort was made to make sure that the information and instructions in this manual were both accurate and current at the time the man- ual was written.
  • Page 8: General Safety

    Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc. Automatic Standby Generator Owner’s Manual...
  • Page 9: Exhaust Hazards

    • This is an Automatic Standby Generator, the generator may crank and start at any time when utility is lost. When this occurs, load circuits are transferred to the STANDBY (generator) power source. To prevent injury, before working on this generator (for inspection, service or mainte- nance), always put the generator into the OFF mode and remove the 7.5 Amp fuse from the generator control panel.
  • Page 10 (NEC 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy. Automatic Standby Generator Owner’s Manual...
  • Page 11: Section 2 - General Information

    Figure 2-1: GH-410 Engine 8 kW Unit CONTROL PANEL DATA LABEL (SEE SAMPLE) DIPSTICK AIR FILTER CIRCUIT BREAKERS EXHAUST ENCLOSURE FUEL INLET (BACK) FUEL REGULATOR COMPOSITE BASE BATTERY COMPARTMENT OIL FILTER OIL FILL CAP Figure 2-2: GH-530 Engine 11 kW Unit Automatic Standby Generator Owner’s Manual...
  • Page 12: Protection Systems

    Am alarm will shut the generator down to protect the system from any damage. In the event of an alarm, an owner can clear the alarm and restart the generator prior to contacting their independent servicing dealer. If the intermittent issue occurs again, contact your independent servicing dealer. Automatic Standby Generator Owner’s Manual...
  • Page 13: Emission Information

    Intake Pipe / Manifold • Air Cleaner • Fuel Metering System • Carburetor / Mixer Assembly • Fuel Regulator • Ignition System • Spark Plug • Ignition Module • Exhaust System • Exhaust Manifold • Muffler Automatic Standby Generator Owner’s Manual...
  • Page 14: Specifications

    50 Amp 65 Amp 90 Amp 100 Amp Phase Rated AC Frequency 60 Hz Battery Requirement Group 26R, 12 Volts and 525 CCA Minimum (Generac Part No. 0H3421S) Weight (unit only in lbs./kilos) 360/163.3 407/184.6 471/213.6 451/204.6 476/216 Enclosure Steel...
  • Page 15: Accessories

    Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas 2.4.4 — Battery Requirements Group 26R, 12V, minimum 525CCA (Generac Part No. 0H3421S). For proper battery maintenance procedures, see Section 4 Maintenance. 2.4.5 — Battery Charger The battery charger is integrated into the control panel module in all models.
  • Page 16 This extended coverage is applicable to registered units and end-user proof of purchase must be available upon request. Available for Generac ®, Guardian ® and Centurion ® products. Not available for Corepower™ and EcoGen products or all international purchases. Contact an independent authorized Dealer for additional information on accessories.
  • Page 17: Section 3 - Operation

    Then, place a “DO NOT OPERATE” tag on the generator panel and on the transfer switch. NOTE: The generator is to be run with all appropriate panels in place, including during troubleshooting by a technician. Automatic Standby Generator Owner’s Manual...
  • Page 18: Using The Auto/Off/Manual Buttons

    To get to the MENU, use the “Escape” button from any page. It may require pressing it many times before getting to the MENU page. Navigate to ↑ ↓ the desired menu by using the buttons. When the desired menu is displayed and flashing, press the “Enter” button. See Figure 3-3. Automatic Standby Generator Owner’s Manual...
  • Page 19 Figure 3-3: Navigation Menu Automatic Standby Generator Owner’s Manual...
  • Page 20: Automatic Transfer Operation

    Will not exercise if generator is already running in either AUTO or MANUAL mode. • During exercise, the controller will only transfer if utility fails during exercise for 10 seconds, and will switch to AUTO. Automatic Standby Generator Owner’s Manual...
  • Page 21: Turning The Generator Off When Operating Under Load

    Allow the engine to stabilize and warm up for a few minutes. Set the Main Circuit Breaker (Generator Disconnect) to its ON (CLOSED) position. The standby power source now powers the loads. Figure 3-4: Manual Transfer Switch Operation Automatic Standby Generator Owner’s Manual...
  • Page 22 5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their UTILITY posi- tions (loads connected to the utility power source). 6. Turn on the utility power supply to the transfer switch using the means provided. 7. Press the Control Panel AUTO button. Automatic Standby Generator Owner’s Manual...
  • Page 23: Side Compartment

    The battery charger operates as a “Smart Charger” that ensures: • Output is continually optimized to promote maximum battery life. • Charging levels are safe. NOTE: A warning is displayed on the LCD when the battery needs service. Automatic Standby Generator Owner’s Manual...
  • Page 24: Setting The Exercise Timer

    1800 0 sec 10 s 15 s 20 s 25 s 30 s 35 s 40 s 45 s 1 min 5 min Exercise Time Figure 3-7: Low Speed Exercise Profile - 22 kW Units Automatic Standby Generator Owner’s Manual...
  • Page 25 Low Speed Exercise Pr - 16 to 20 kW Generators 3200 3000 2800 2600 2400 2200 2000 1 min 5 min Exercise Time Figure 3-8: Low Speed Exercise Profile - 16-20 kW units Automatic Standby Generator Owner’s Manual...
  • Page 26 This page intentionally left blank. Automatic Standby Generator Owner’s Manual...
  • Page 27: Section 4 - Maintenance

    Maintenance Section 4 NOTE: Proper maintenance and proper and safe operation is crucial to the life of the generator. Genuine Generac parts MUST be used to ensure warranty coverage NOTE: Since most maintenance alerts occur at the same time (most have two year intervals), only one will appear at any one time.
  • Page 28: Checking Engine Oil Level

    Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing so could damage the engine. Hot oil may cause burns. Avoid prolonged or repeated skin exposure with used oil. Thoroughly wash exposed areas with soap. Automatic Standby Generator Owner’s Manual...
  • Page 29 4.3.1— Engine Oil Recommendations To maintain the warranty, genuine Generac replacement parts MUST be used, including Generac oil kits (which include an oil and air filter). Gen- erac oil kits can be obtained through an Authorized Dealer or purchased on-line. To purchase on-line, access the maintenance kits page through www.generac.com or directly at shop.generac.com.
  • Page 30: Changing The Engine Air Cleaner

    Check the spark plug gap using a wire feeler gauge. See Figure 4-3. Adjust the gap by carefully bending the ground electrode to: • For 8, 11, 20 and 22 kW units - 0.76 mm (0.030 in) • For 16 kW units - 1.02 mm (0.040 in) Figure 4-3: Spark Plug Gap Adjustment Automatic Standby Generator Owner’s Manual...
  • Page 31: Valve Lash Adjustment

    Torque fasteners to 6-9 ft/lb (8-12 Nm) • Install spark plugs. Torque to 15-18 ft/lb (20-25 Nm). • Re-attach the spark plug wire to the spark plug. • Repeat the process for the other cylinder, if necessary. Automatic Standby Generator Owner’s Manual...
  • Page 32: Battery Maintenance

    Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metallic objects on top of the battery. • Disconnect the charging source prior to connecting or disconnecting battery terminals. Automatic Standby Generator Owner’s Manual...
  • Page 33: Attention After Submersion

    Attach a tag to the engine indicating the viscosity and classification of the new oil in the crankcase. 10. Remove the spark plug(s) and spray a fogging agent into the spark plug(s)’ threaded openings. Reinstall and tighten the spark plug(s). Automatic Standby Generator Owner’s Manual...
  • Page 34 12. Turn on the utility power to the transfer switch. 13. Set the Control Panel to AUTO. The generator is ready for service. NOTE: When a battery is dead or has been disconnected, the exercise timer and current date and time must be reset. Automatic Standby Generator Owner’s Manual...
  • Page 35: Section 5 - Troubleshooting

    Adjust oil to proper level. amounts of oil. Engine breather defective. Improper type or viscosity of oil. See “Engine Oil Recommendations”. Damaged gasket, seal or hose. Check for oil leaks. *Contact an Authorized Service Dealer for assistance. Automatic Standby Generator Owner’s Manual...
  • Page 36 This page intentionally left blank. Automatic Standby Generator Owner’s Manual...
  • Page 37: Section 6 - Quick Reference Guide

    UNDER Unit will not start in AUTO with utility LEDs/Screen Contact servicing dealer. VOLTAGE loss. for alarms. Check the Unit will not start in AUTO with utility UNDERSPEED LEDs/Screen Contact servicing dealer. loss. for alarms. Automatic Standby Generator Owner’s Manual...
  • Page 38 SERVICE B Yellow LED illuminated in any state. YELLOW for additional press ENTER to clear. information. Check screen Inspect Battery Yellow LED illuminated in any state. YELLOW for additional Inspect battery; press ENTER to clear. information. Automatic Standby Generator Owner’s Manual...
  • Page 40 Part No. 0K5801 Rev. A 04/17/2014 Printed in USA Generac Power Systems, Inc. © Generac Power Systems, Inc. All rights reserved S45 W29290 Hwy. 59 Specifications are subject to change without notice. Waukesha, WI 53189 No reproduction allowed in any form without prior written 1-888-GENERAC (1-888-436-3722) consent from Generac Power Systems, Inc.