Carrier Performance TP-PRH-A Installation Instructions Manual

Carrier Performance TP-PRH-A Installation Instructions Manual

Performance series edge thermidistat control
Hide thumbs Also See for Performance TP-PRH-A:
Table of Contents

Advertisement

TP ---PRH---A, ---B, TP ---NRH---A, ---B
Performance™ Series
Edger Thermidistat™ Control
Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1,
US6956463 B2.
Installation Instructions
A07049
Designed and Assembled
A07048
Non- - Programmable Control
in the USA.

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Performance TP-PRH-A

  • Page 1: Installation Instructions

    TP ---PRH---A, ---B, TP ---NRH---A, ---B Performance™ Series Edger Thermidistat™ Control Installation Instructions A07049 A07048 Programmable Control Non- - Programmable Control Designed and Assembled in the USA. NOTE: Read the entire instruction manual before starting the installation. US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS ....... . INTRODUCTION ......... . INSTALLATION CONSIDERATIONS .
  • Page 4: Introduction

    - configured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Carrier’s proven line of thermostats; it provides separate setpoints for heating and cooling in addition to humidification and dehumidification.
  • Page 5: Installation Considerations

    INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low- - voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper.
  • Page 6 AC or HP, 1- - or 2- - speed compressor, and for Hybrid Heatt installations, allowing it to be used in place of all Carrier thermostats. Programmable Thermidistat Controls may be configured as non- - programmable if user desires.
  • Page 7 WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM terminal. This will bypass furnace safety controls. See Low Voltage Wiring Diagrams and notes for proper connection. Dehumidify Equipment and Connections The dry contact output connects to the dehumidify input on variable- - speed furnaces and fan coils.
  • Page 8 Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable model, where it is desirable to install the Thermidistat Control in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
  • Page 9: Installation

    INSTALLATION CAUTION UNIT DAMAGE HAZARD Failure to follow the recommended wiring practices could result in damage to the wall control and personal property. Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power.
  • Page 10 A13295 Fig. 2 - - Coil Excess Wiring A07685 Fig. 3 - - TP- - PRH- - A, - - B Carton Contents...
  • Page 11 Carton contains the following components. See Fig. 3 for TP- - PRH- - A, - - B or Fig. 4 for TP- - NRH- - A, - - B: 1. Display Module 2. Stand- - off for Equipment Control Module 3.
  • Page 12 Close to or in a frequently used room, preferably on an inside partition- ing wall. On a section of wall without pipes or duct work. Thermidistat Control should NOT be mounted: Close to a window, on an outside wall, or next to a door leading to the outside.
  • Page 13 CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1.
  • Page 14 CAUTION ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage. Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly. Two- -Piece Installation The following steps should be followed for the installation of the two- - piece configuration.
  • Page 15 A07225 Fig. 5 - - Press Tabs to Remove Backplate A07226 Fig. 6 - - Take Apart...
  • Page 16 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. See Fig.
  • Page 17 6. Match and connect equipment wires to proper terminals of each connector block, being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Mod- ule to the Thermidistat Control mounting base. If wires are connected incor- rectly, the Display Module will not operate.
  • Page 18 A07166 Fig. 9 - - Secure Wires to Terminal Strip A07167 Fig. 10 - - Connect Pigtail Wires to Display Module...
  • Page 19 NOTE: The 2- - wire pigtail is not intended to support the weight of the Display Module. Do not hang the Display Module from the Equipment Control Module screw terminals. Red of the pigtail is V+ Black of the pigtail is Vg 7.
  • Page 20 10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 12. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.). A07217 Fig.
  • Page 21 A07227 Fig. 13 - - Standoff NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Mod- ule to the Thermidistat Control mounting base.
  • Page 22 A07218 Fig. 14 - - Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- - digit code appears on large display which identifies Thermidistat Control configuration.
  • Page 23 Single- -Piece Installation The following steps should be followed for the installation of the single- - piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equip- ment Control Module.
  • Page 24 A07219 Fig. 15 - - Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incor- rect temperature and/or humidity measurement.
  • Page 25 A07220 Fig. 16 - - Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- - digit code appears on large display which identifies Thermidistat Control configuration.
  • Page 26 Set Thermidistat Control Configuration Configuration options enable the installer to configure the Thermidistat Control for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual.
  • Page 27 Option 11 — Adjustable Setpoint Deadband (not available on heat only and cool only systems) Option 12 — Smart Recovery (programmable models only) Option 13 — Room Temperature Offset Adjustment Option 14 — Humidity Offset Adjustment Option 15 — Enable Auto Mode Option 16 —...
  • Page 28 Option 31* — Daylight Savings Time Configuration (programmable models only) Option 32 — Furnace Heat Staging Option 33 — Single or Two- - Piece Installation Option 34 — Hybrid Heat Furnace Latch Option 40 — Fan Humidify Option 41 — Variable Speed Blower Option 42 —...
  • Page 29 Configuration Options —Selection Option 01 — Equipment Type Range: H2, A2, HP, AC, hh, h2, H, C H2 — operates a two- - speed heat pump with a fan coil HP — operates a single- - speed heat pump with a fan coil A2 —...
  • Page 30 Option 03 — Fahrenheit/Centigrade Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is Fahrenheit (F). Option 04 — Fan (G) On With W/W1 This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On.
  • Page 31 This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr).
  • Page 32 Option 09 — Heat Pump Lockout Temperature Balance Point (only available when heat pump is used and when outdoor air temperature sensor is present) This selection is only available on Hybrid Heat systems. A Hybrid Heat system is selected via the Option 1 Equipment Type configuration. Configurations settings are: OF (off), 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
  • Page 33 Option 11 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. The selection allows the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1 thru 6. Default is 2.
  • Page 34 to automatically change between heating mode and cooling mode when sufficient demand for heating or cooling exists. On — Auto mode is available. OF — Auto mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the Thermidistat Control allows the system to operate.
  • Page 35 Option 18 — Backlight Configuration When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed.
  • Page 36 Option 19 — Dry Contact Configuration (non- - programmable models only) OF — The dry contact is always de- - energized. ON — The dry contact will operate as a DH relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint, the dry contact D1- - D2 will be opened.
  • Page 37 2 — The user has access to change the setpoints only. 3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed. When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds.
  • Page 38 Option 22 — High Cool Latch Temperature (only available if outdoor sensor is present) An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off).
  • Page 39 20 to 50_F (- - 7 to 10_C) — Outdoor temperature below which both first and second stages of the compressor are energized to satisfy all heating demands. When a cycle starts under a high heat latch, it will finish the heating cycle on high stage. On —...
  • Page 40 Default is 52_F/11_C (based on the adjustable deadband default = 2). Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband.
  • Page 41 Option 30 — Programmable Fan (programmable models only) This selection allows the homeowner to program the fan selection to “Auto” or “On” fan operation for each of the program schedule periods. This selection is only available on programmable Thermidistat Controls. OF (off) —...
  • Page 42 by pressing the up button and “On” is displayed. The setting shall be left “On” to enable the Daylight Savings Time function. Default is On (on). Option 32 — Furnace Heat Staging Control (available only when the Thermidistat Control is configured to operate AC or A2 equipment). 1 —...
  • Page 43 Option 34 - - Hybrid Heat Furnace Latch This selection allows a Hybrid Heat system to finish a heating cycle using the furnace. On - - Once the furnace is on, it will finish the heating cycle with the furnace. If a heat pump defrost occurs, the heating cycle will finish with the furnace.
  • Page 44 Off - - The system has a single speed (PSC) blower. On - - The system has a variable speed blower. Select Off for geothermal applications. Factory default is OF (Off) Option 42 — Variable Speed Super Dehumidification This option will only be available if the Variable Speed Blower setup (Option 41) has been set to ON.
  • Page 45 Option 44 — Super Comfort Heat This option is only available on heat pump units HP (HP, H2, hh, and h2) when Option 41 (Variable Speed Blower) is set to On and the system has a valid OAT sensor. OF (Off) - - Comfort Heat is off On - - Comfort Heat feature is on.
  • Page 46 Option 99 — Reset to Factory Defaults Use this capability to reset the Thermidistat Control to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and calendar which have been manually entered will be lost! When this option is selected, the configuration number (99), will appear on the left and 10 will appear on the right.
  • Page 47: System Start- -Up And Checkout

    SYSTEM START- -UP AND CHECKOUT The Thermidistat Control is designed with a built- - in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds.
  • Page 48 In a heat pump application, when the mode is set to “em heat” the auxiliary heat will turn on for 3 minutes. The clock display will count down from 180 to 0 during this test. TO TEST FAN Fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on.
  • Page 49 If the programmed schedule is to be used, make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on. Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE, HOLD and VACATION selections. If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon next to HOLD.
  • Page 50 When changing Vacation settings, the soft keys are used to choose the selection to be adjusted and the UP/DOWN buttons are used to change the setting. Humidify setting may only be changed when heat mode is selected and Dehumidify setting may only be changed when cool mode is selected.
  • Page 51 2. Auto Humidify Thermidistat Control will automatically adjust the humidity setpoint accord- ing to the outdoor temperature. As the outdoor temperature decreases, the humidity setpoint also decreases. Settings ranging from 1 to 9, 1 being the lowest and 9 the highest, will be visible to the homeowner. See Fig. 18 for outdoor temperature/indoor humidity relationship in auto humidify mode.
  • Page 52 Dehumidification Dehumidification is done only during cooling. Depending on type of equipment used, compressor speed, blower speed, setpoint adjustment, and equipment cycling are modified to provide added dehumidification. A dehumidification setpoint (separate from humidification setpoint) is available to the homeowner. It can range from 46% to 66% relative humidity.
  • Page 53 point change is internal to the Thermidistat Control and is not shown on the display. A06599 Fig. 18 - - Auto Humidity 3. Dehumidify Off Dehumidification can be turned off completely. This can be done without changing existing setpoints.
  • Page 54 To Select Dehumidification (programmable - - between NORMAL, COOL TO, and OFF) Press the soft key below the dehumidify icon button to bring up dehumidify selections. Dehumidify options are only available when in Cooling mode. When system is in AUTO mode, dehumidify options are available if the last system operation was a call for cooling.
  • Page 55 - - output is turned On when no dehumidify demand exists and is turned OFF when demand exists. Carrier FK and FV series variable- - speed fan coils, all variable- - speed furnaces, and select single and multi- - stage furnaces with the dehumidify connection have dehumidify inputs which connect directly to Thermidistat Control dry contact.
  • Page 56 Vacation Setpoints A special set of temperature and humidity setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 3 for default values.
  • Page 57: Operational Information

    OPERATIONAL INFORMATION Timers Five- - Minute Compressor Timeguard This timer prevents compressor from starting unless it has been off for at least 5 minutes. It can be overridden for 1 cycle by simultaneously pressing FAN and UP buttons. Cycle Timer Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes.
  • Page 58 Defrost When defrost occurs in a Hybrid Heat system, the furnace will operate during the defrost cycle. At the end of the defrost cycle, the furnace and heat pump will be de- - energized while the fan is energized for 2 minutes allowing the heat exchanger to cool down.
  • Page 59 Heat/Cool Setpoints (Desired Temperature) A minimum difference of 1_ and maximum of 6_ is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference. This difference is adjustable via Configuration Option Equipment On Indicators When cooling equipment is on, a COOL ON icon is displayed.
  • Page 60 Programmable Fan (programmable models only) The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO. If the fan button is pressed to change from On to Auto or vice versa when programmable fan has been enabled, the manual change will only remain in effect until the next program period, when the programmable fan setting will be changed per the scheduled setting.
  • Page 61 Relays This thermostat uses latching relays. When the thermostat loses power, the relays will remain in their last position until power is restored and all relays are reset to their correct position. Out of the box, the outputs may appear to be On when the thermostat is not powered.
  • Page 62: Troubleshooting

    TROUBLESHOOTING If the display module doesn’t power up after power is applied, check the Rc/Rh and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg and V+. This voltage will be approximately 12- - 20VDC. If voltage is present, check the polarity to make sure it is wired correctly.
  • Page 63 E5 - - If Thermidistat Control cannot properly read humidity, E5 will be displayed. Replace Thermidistat Control. If both Humidify and Dehumidify have been set to OF, the humidity value will be shown as “- - - - ” when viewed from the humidity menu, but no E5 will be shown in the display.
  • Page 64 Table 4 – Equipment Configuration Outputs Equip Tstat COOL COOL HEAT HEAT HEAT HEAT EM HEAT HEAT Config Model STG 1 STG 2 STG 1 STG 2 STG 3 STG 4 STG 2 STG 1 TP--PRH-- W/W1, SS AC A, --B Y/Y2 ---- W/W1...
  • Page 65 Table 4 - - Equipment Configuration Outputs (cont.) Equip Tstat COOL COOL HEAT HEAT HEAT HEAT EM HEAT HEAT Config Model STG 1 STG 2 STG 1 STG 2 STG 3 STG 4 STG 2 STG 1 2SPD HP TP--PRH Y1/W2 Y1/W2, Opt 1 = H2...
  • Page 66 WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module Fan Coil Heat Pump RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Y/Y2 Y1 / W2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Outdoor Air Temp Remote Room Sensor...
  • Page 67 Fan Coil Heat Pump Equipment Control Module RVS Cooling O/B W2 Heat Stage 3 W/W1 Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 jumper for Dry Contact 1 Dehumidify modes Dry Contact 2...
  • Page 68 Typical Single-Stage Equipment Control Module Fan Coil Heat Pump RVS Cooling O/B W2 Heat Stage 2 W/W1 Heat Stage 3 Y1 / W2 Heat/Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp...
  • Page 69 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 Aux. Connection 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor *...
  • Page 70 Equipment Control Module Fan Coil Air Conditioner Remove J2 Heat Stage 2 O/B W2 Jumper for heat staging Heat Stage 1 W/W1 Cool Stage 1 Y1 / W2 Cool Stage 2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 jumper for Dry Contact 1 Dehumidify...
  • Page 71 Typical Single-Stage Fan Coil Air Conditioner Equipment Control Module Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve *...
  • Page 72 Fan Coil Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 Aux. Connection 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor...
  • Page 73 Equipment Control Module Fan Coil Heat Pump RVS Cooling O/B W2 Remove J2 Heat Stage 2 W/W1 Jumper for Heat Stage 3 Y1 / W2 heat staging Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 Jumper for Dry Contact 1 Dehumidify...
  • Page 74 Typical Fan Coil Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor...
  • Page 75 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN A09172...
  • Page 76 Equipment Control Module Fan Coil Air Conditioner Remove J2 Heat Stage 2 O/B W2 Jumper for heat staging Heat Stage 1 W/W1 Y1 / W2 Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating Remove J1 24VAC Hot Cooling Jumper for Dehumidify Dry Contact 1 modes...
  • Page 77 Typical Single-Stage Equipment Control Module Fan Coil Air Conditioner RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp...
  • Page 78 Equipment Control Module Furnace Heat Pump RVS Cooling O/B W2 Heat Stage 3 W/W1 W/W1 W2** (furnace) Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 DHUM Dry Contact 2 24VAC Common Humidify Humidifier Solenoid...
  • Page 79: Hybrid Heat

    Single-Stage Furnace Heat Pump Equipment Control Module RVS Cooling O/B W2 W2** Heat Stage 2 W/W1 (furnace) Heat Stage 2 Y1 / W2 Y/Y2 Heat/Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify...
  • Page 80 Furnace Air Conditioner Equipment Control Module Heat Stage 2 O/B W2 W/W1 Heat Stage 1 W/W1 Cool Stage 1 Y1 / W2 Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify...
  • Page 81 Single-Stage Equipment Control Module Furnace Air Conditioner O/B W2 Heat Stage 1 W/W1 Y1 / W2 Y/Y2 Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor *...
  • Page 82 Furnace Heat Pump Equipment Control Module RVS Cooling O/B W2 W2** Heat Stage 3 Y1 / W2 W/W1 (furnace) Heat Stage 2 W/W1 (furnace) Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify...
  • Page 83 Equipment Control Module Furnace O/B W2 Heat Stage 1 W/W1 Y1 / W2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 DHUM Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor * OAT/RRS Com SRTN...
  • Page 84 Equipment Control Module Furnace Air Conditioner Heat Stage 2 O/B W2 W/W1 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve *...
  • Page 85 Equipment Control Module Furnace Air Conditioner Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 DHUM Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor...
  • Page 86 THERMIDISTAT CONTROL CONFIGURATION RECORD Installer Model Number Date _________________________ ______________________________ ________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C.
  • Page 87 E Configuration Options Option 01 ____ Equipment Type Option 02 ____ Clean Filter Timer Adjustment Option 03* ____ Fahrenheit/Centigrade Selection Option 04 ____ Fan (G) on with W/W1 Selection Option 05 ____ Room Air Temperature Sensing (programmable models only) Option 06 ____ Cooling Lockout Below 55_F/13_C Selection (only available if outdoor air sensor is present) Option 07...
  • Page 88 E Configuration Options (cont) Option 19 ____ Dry Contact (programmable models only) Option 20 ____ Outdoor Air Temperature Offset Adjustment Option 21* ____ Keypad Lockout Option 22 ____ High Cool Latch Temperature Option 23 ____ High Heat Latch Temperature Option 24* ____ Programmable/Non- - Programmable (programmable models only) Option 25*...
  • Page 89 NOTES...
  • Page 90 NOTES...
  • Page 92 997---060360---10---R Copyright 2013 Carrier Corporation 7310 W Morris St. Indianapolis, IN 46231 TP---PRH ---10SI Replaces: TP--- PRH--- 09SI Edition Date: 07/13 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents