Carrier AQUAZONE 50QE900 Installation And Operating Instructions Manual

Water source heat pump commercial programmable thermostat

Advertisement

Installation and Operating Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Select Thermostat Location . . . . . . . . . . . . . . . . . . . . . . 1
Install Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Set Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Pump Configuration . . . . . . . . . . . . . . . . . . . . . . . . 3
Configure Advanced Setup. . . . . . . . . . . . . . . . . . . . . . . 3
Program Thermostat Schedules. . . . . . . . . . . . . . . . . . 4
Calibrate Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Check Thermostat Operation. . . . . . . . . . . . . . . . . . . . . 6
Final Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Auto-Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Two-Stage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Clock Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Holiday Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Keypad Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
IMPORTANT: Read entire instructions before starting
the installation.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Fol-
low all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper
wiring or installation may damage thermostat.
Recognize safety information. This is the safety alert sym-
bol
. When the safety alert symbol is present on equipment
or in the instruction manual, be alert to the potential for person-
al injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a haz-
ard which could result in personal injury or death. CAUTION
is used to identify unsafe practices which would result in minor
personal injury or property damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500037-01
Book 1
4
Tab
5a
5a
50QE900 Water Source Heat Pump
Commercial Programmable Thermostat
Part Number 50QE900-220WS
Printed in U.S.A.

GENERAL

The 7-day, commercial, programmable thermostats is a
wall-mounted, low-voltage thermostat which maintains room
temperature by controlling the operation of an HVAC (heating,
cooling and ventilation) system. Separate heating and cooling
set points and auto-changeover capability allow occupied and
unoccupied programming for energy savings.
This thermostat allows up to 4 time/temperature settings to
be programmed per 24-hour period. Each thermostat stores
programs for 7 independent days. Batteries are not required.
During power interruption the internal NEVERLOST™ mem-
ory stores programmed schedules for an unlimited time while
the clock continues to run for at least 48 hours.
The thermostat can be configured to accept several different
equipment configurations, and is provided for heat pump
operation.

INSTALLATION

Select Thermostat Location -

be mounted:
• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an
inside partitioning wall
• on a section of wall without pipes or ductwork
• where temperature operating limits are within 41 to
104 F (5 to 40 C)
• where humidity operating range is within 0 to 95% rela-
tive humidity, non-condensing
The thermostat should NOT be mounted:
• close to a window, on an outside wall, or next to a door
leading to the outside
• where exposed to direct light and heat from a lamp, the
sun, a fireplace, or any other temperature-radiating
object which may cause a false reading
• close to or in direct airflow from supply registers or
return-air grilles
• in areas with poor air circulation (such as behind a door
or in an alcove)
Form 50QE-7SI
AQUAZONE™
The thermostat should
Pg 1
7-07
Replaces: 50QE-2SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AQUAZONE 50QE900

  • Page 1: Table Of Contents

    AQUAZONE™ 50QE900 Water Source Heat Pump Commercial Programmable Thermostat Installation and Operating Instructions Part Number 50QE900-220WS CONTENTS GENERAL SAFETY CONSIDERATIONS ..... . 1 The 7-day, commercial, programmable thermostats is a wall-mounted, low-voltage thermostat which maintains room GENERAL .
  • Page 2: Install Thermostat

    7. Secure mounting base to wall with 2 screws and anchors Install Thermostat provided. Ensure all wires exit through hole in mounting base. 8. Adjust wire length and routing to allow proper closure of Before installing thermostat, turn off all power to the unit. the thermostat.
  • Page 3: Set Clock

    The Set Clock button allows the user to Set Clock — change the time and day displayed on the thermostat. Press the Set Clock button. The current time will blink on and off. Press the UP ARROW and DOWN ARROW buttons until the cor- Thermostat rect time is shown.
  • Page 4: Program Thermostat Schedules

    DEADBAND (Step 5) — The deadband is the difference in Before pro- Program Thermostat Schedules — temperature above the cooling set point or below the heating gramming the thermostat, plan the thermostat daily schedule. set point that the thermostat will wait before turning on the first The schedule is divided into 7 days (Monday through Sunday).
  • Page 5: Calibrate Sensor

    Table 3 — Daily Schedule Planner SCHEDULE OF THE Occupied 1 Occupied 2 Occupied 3 Unoccupied WEEK Start / Stop / Heat / Cool Start / Stop / Heat / Cool Start / Stop / Heat / Cool Heat / Cool Monday Tuesday Wednesday...
  • Page 6: Check Thermostat Operation

    point is equal to or greater than the set point plus the deadband To check thermo- Check Thermostat Operation — plus 2 degrees. stat operation, perform the following procedure: 1. Press the Mode button repeatedly until the Heat icon In the event of a power loss, the ther- Clock Backup —...
  • Page 7: Troubleshooting

    TROUBLESHOOTING Table 4 — Thermostat Troubleshooting PROBLEM SOLUTION Display On Thermostat Not Illuminated. Check for 24 vac at the R terminal connection. Terminal R must be connected for proper thermostat operation. ‘‘Service Filter’’ Is Displayed On Thermostat. After the configured number of blower operating hours, the Service Filter message will be displayed.
  • Page 8 Copyright 2007 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 Catalog No. 04-53500037-01 Printed in U.S.A. Form 50QE-7SI Pg 8 7-07 Replaces: 50QE-2SI...