ESL 570N Smoke Detector
Model: 572NS

Installation Instructions

Description
The ESL 572NS smoke detector must be used as part of a
wireless system and requires a transmitter.
The detector provides the following features:
CleanMe Self-diagnostics monitors its own sensitivity and
operational status. If the detector drifts out of the UL listed
sensitivity range or fails internal diagnostics, it extinguishes
its LED and sends a trouble signal to the control panel.
Tamper switch sends a trouble signal to the control panel
when the detector is removed from its mounting base.
Transmitted Signal Outputs
Once a wireless transmitter is installed, the detector can
transmit the following signals to the control panel:
• Alarm
• Alarm restore
• Low battery
Optional
temperature
sensor
Test
button
Figure 1 - Detector Features
ESL 572NS Smoke Detector
• CleanMe
• Maintenance alert
• Tamper
LED
Sounder vent
Optional
temperature
sensor
CSFM
4300 Series
Wireless Smoke Alarm
Installation Guidelines
Selecting a suitable location is critical to the operation of
smoke detectors. This equipment should be installed in
accordance with the National Fire Protection Association's
(NFPA) Standard 72, Chapters 2 and 8. Depending on the
application, you may need to reference other chapters of
NFPA 72 or NFPA 101.
Since regulations pertaining to smoke detector installation vary
from state to state, contact the authority having jurisdiction
(AHJ). Where public safety is primary, the AHJ may be a
federal, state, local, or other regional department or individual
such as a fire chief, fire marshal, chief of a fire prevention
bureau, labor or health department, building official, electrical
inspector, or others having statutory authority. For insurance
purposes, an insurance inspection department, rating bureau,
or other insurance company representative may be the AHJ. In
some cases, the property owner or their designated agent
assumes the role of the AHJ. At government installations, the
commanding officer or department official may be the AHJ.

General Guidelines

Locate the detector in evironmentally controlled areas
where the temperature range is between 40° and 100° F
(4.4° and 37.8° C) and the humidity is between 0 and 90%
noncondensing.
Locate detectors away from ventilation sources that can
prevent smoke from reaching the detector.
Locate ceiling mounted detectors in the center of the room
or hallway, at least 4 inches (10cm) away from any walls or
partitions.
Locate wall mounted detectors so the top of the detector
is 4 to 12 inches (10 to 31cm) below the ceiling.
In rooms with sloped, peaked, or gabled ceilings, locate
detectors 3 feet (.9 meters) down or away from the highest
point of the ceiling.
When mounting to suspended ceiling tile, the tile must be
secured with the appropriate fastener to prevent tile
removal.
OEM
Accounts
Only
1

Advertisement

loading

Summary of Contents for GE ESL 570N

  • Page 1: Installation Instructions

    CSFM ESL 570N Smoke Detector Accounts Model: 572NS 4300 Series Only Wireless Smoke Alarm Installation Instructions Description Installation Guidelines The ESL 572NS smoke detector must be used as part of a Selecting a suitable location is critical to the operation of wireless system and requires a transmitter.
  • Page 2: Locations To Avoid

    detection devices shall not be required to be installed O f f i c e O f f i c e O f f i c e O f f i c e O f f i c e throughout an entire room or building. I n c o m m e r c i a l b u i l d i n g s a s m o k e d e t e c t o r NFPA 72, 2-2 Heat-Sensing Fire Detectors Heat-sensing fire C o n f e r e n c e R o o m...
  • Page 3 communication between the control panel and the detector Alignment arrow before permanently mounting the detector as follows: Alignment tab - Hold the detector up where you plan to install it. - Press the Test button on the detector for 4 seconds. The detector sends a signal to the control panel.
  • Page 4: Cleaning The Detector

    Attaching and Removing the Detector When to Replace the Batteries To remove the detector from the mounting base, grasp the The smoke detector requires two 3V lithium 123 batteries as listed detector and turn it counterclockwise approximately 15 on the battery compartment cover. The required batteries are degrees.
  • Page 5: Maintaining The Detector

    Important: The control panel alarm and all auxiliary functions During the warranty period, if a GE Interlogix product or any of its should be verified for a complete test of the system. components becomes defective, it will be repaired or replaced without charge.
  • Page 6: Specifications

    Replacement smoke chambers (set of 10) 60-933 6 pack 3V lithium batteries GE Interlogix www.GE-Interlogix.com 12345 SW Leveton Drive Tualatin, OR 97062 Phone: 503-692-4052 USA & Canada: 800-547-2556 Technical Service: 800-648-7424 FaxBack: 800-483-2495 1039260-Rev B 04/03 © 2003 GE Interlogix ESL 572NS Smoke Detector...