A Specifications

Power Requirements

Table A-1. HP NetServer LC 2000/2000r Input Power
Input Voltage and Frequency
Maximum inrush current
Delayed action circuit breaker
recommended
NOTE
Some local codes do not allow 16-amp service for a 16-amp
device. Consult a qualified electrician or local regulatory
authority before beginning electrical site preparation.
Table A-2. HP NetServer LC 2000/2000r Power Ratings
AC Input
Maximum Input
Voltages
Power (VA)
100 VAC
545
120 VAC
531
208 VAC
516
230/240 VAC
514
100-240 VAC 10%; 50/60 Hz
8 AMPs peak (for 1 power supply) 120 VAC
or 32 AMPs peak (2 power supplies)
16 AMPs peak (for 1 power supply) 240 VAC
or 32 AMPs peak (2 power supplies)
North America: a 20 A minimum delayed action
circuit recommended for each 16 A power
distribution unit (PDU) that is connected to an HP
NetServer LC 2000/2000r.
Europe (single server in a rack): use a
16 A-minimum circuit with one IEC MCB
C-type breaker for each 16-Amp PDU.
Europe (multiple servers in a rack): use a
16-amp-minimum circuit with one IEC MCB
D-type breaker for each 16 A PDU.
Maximum Input
Maximum Operating
Power (W)
Current RMS (AMPS)
540
525
506
504
5.5
4.5
2.5
2.3
161