Installer Setup
Number (Press
Time
Select
change)
Adaptive
Intelligent
Recovery™
control.
Degree
temperature
display
Not Used.
Clock format.
Not Used.
17 thru 23
Outdoor
temperature
display (models
with OT
terminals).
Not Used.
25 thru 28
O/B terminal
energized in
heating or
cooling.
Deadband
Not Used.
31 and 32
Minimum off
time for the
compressor.
Temperature
range stops in
heating.
Temperature
range stops in
cooling.
Not Used.
T8611G CHRONOTHERM
Table 3. Thermostat Installer Setup Options. (Continued)
Factory Setting
key to
Display
13
0
Adaptive Intelligent
Recovery™
control is activated
(system starts
early so setpoint is
reached by start of
program period).
14
1
Temperature is
displayed in °C
15
16
0
12-hour clock
format.
24
0
No outdoor
temperature is
displayed.
29
0
O/B terminal
energized for
reversing valve in
cooling.
30
3
Heating and
cooling setpoints
can be set no
closer than 3°F
(1.5°C).
33
5
5 minute minimum
off time for the
compressor.
34
90
Highest heating
setpoint setting.
35
45
Lowest cooling
setpoint setting.
36
®
IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS
(Press
Description
Display
1
1
1
1
4 thru 10
0 thru 4
40 thru 89 Temperature range (1°F
46 thru 99 Temperature range (1°F
5
Other Choices
or
key to change)
Description
Conventional recovery
(system starts recovery at
programmed time).
Temperature is displayed in
°C
24-hour clock format.
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Temperature Sensor to
operate.
O/B terminal energized for
reversing valve in heating
Heating and cooling
setpoints can be set no
closer than the chosen
value:
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Minimum number of minutes
(0 thru 5) the compressor
will be off between calls for
the compressor.
increments) of heating
setpoint settings.
increments) of cooling
setpoint settings
Actual
Setting
69-1406—1