Trane Packaged TerminalAir Conditioners & Heat Pumps Installation Operation & Maintenance

Trane Packaged TerminalAir Conditioners & Heat Pumps Installation Operation & Maintenance

Packaged terminal air conditioners & heat pumps

Advertisement

Packaged T erminal Air
Conditioners & Heat Pumps
PTAC-PRC001-EN
October 2000

Advertisement

Table of Contents
loading

Summary of Contents for Trane Packaged TerminalAir Conditioners & Heat Pumps

  • Page 1 Packaged T erminal Air Conditioners & Heat Pumps PTAC-PRC001-EN October 2000...
  • Page 2: Introduction

    Introduction The new Trane packaged terminal air conditioners (PTACs) and heat pumps are ideally suited for offices, apartments, hotels, motels and institutional homes. Key benefits which make the units a wise choice are: • Energy efficiency • Reliability • Quiet operation •...
  • Page 3: Table Of Contents

    Contents Introduction Features and Benefits Application Considerations Selection Procedure Model Number Description Performance Data Cool and Heat Performance Electric Power Power Connection Wiring Dimension and Weights Mechanical Specifications Options Warranty PTAC-PRC001-EN...
  • Page 4: Features And Benefits

    Features and Benefits Energy Efficiency Automatic Emergency Heat Trane PTAC units and heat pumps are Each unit automatically switches over to among the most efficient in the industry, electric resistance heat if for any reason with EERs of up to 11.6 and COPs of up the heat pump compressor system fails to 3.3.
  • Page 5 Features and Benefits Remote Thermostat Control Special Paint Protection The electrodeposition paint system on Each unit is built to be operated from a the exterior panels assure the unit and remote-mounted thermostat, if desired. wall sleeve will withstand years of Even if it is started without a remote, a moisture and atmospheric pollutants built-in low voltage power source can...
  • Page 6: Application Considerations

    Application Considerations Curtain Wall Installation Block and Brick Veneer Installation Frame and Brick Veneer Installation Panel Wall Installation Panel Wall and Block Veneer Installation Optional Leveling Leg On applications not requiring subbase or leveling legs, unit may be flush mounted to floor. Sleeve Installation Data Framing for Wall Case Framing With Lintel...
  • Page 7: Selection Procedure

    2. Only the following units are available from stock and can normally ship within 3 days after release. 3. Contact your local Trane representative for current stock availability and information on minimum quantity requirements and shipping schedule for special production units.
  • Page 8: Performance Data

    *95 cfm with optional power vent kit. Actual vent cfm performance will vary due to application and installation conditions. Notes: 1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit. 2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
  • Page 9 Notes: 1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit. 2. Heating capacity and efficiency is based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F outdoor coil temperature.
  • Page 10 Performance Data Table PD-4 — PTEC Air Conditioner — 208V WBT Ent DBT Ent Outdoor Temperature (°F) Nominal Indoor Indoor Unit Coil Coil Total Total Total Total Size (°F) (°F) 6680 5695 6380 5545 6030 5665 5710 5530 6930 6930 6665 6665 6270...
  • Page 11 Performance Data Table PD-5 — PTEC Air Conditioner — 230/265V WBT Ent DBT Ent Outdoor Temperature (°F) Nominal Indoor Indoor Unit Coil Coil Total Total Total Total Size (°F) (°F) 6780 5795 6480 5645 6130 5765 5810 5630 7030 7030 6765 6765 6370...
  • Page 12 Performance Data Table PD-6 — PTHC Heat Pump — 208V WBT Ent DBT Ent Outdoor Temperature (°F) Nominal Indoor Indoor Unit Coil Coil Total Total Total Total Size (°F) (°F) 6680 5695 6380 5545 6030 5665 5710 5530 6930 6930 6665 6665 6270...
  • Page 13 Performance Data Table PD-7 — PTHC Heat Pump — 230/265V WBT Ent DBT Ent Outdoor Temperature (°F) Nominal Indoor Indoor Unit Coil Coil Total Total Total Total Size (°F) (°F) 6780 5795 6480 5645 6130 5765 5810 5630 7030 7030 6765 6765 6370...
  • Page 14 Performance Data Table PD-8 — Heating Capacity — Water Heating Capacity (Btu) Hot Water Pressure 7000 & 9000 Btu Units 12000 Btu Units 15000 Btu Units Drop (psig) 200°F EWT 180°F EWT 200°F EWT 180°F EWT 200°F EWT 180°F EWT 2-Way Fan Speed Fan Speed...
  • Page 15: Electric Power

    3. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included and factory installed on Trane chassis). 4. Total watts for 7,000 and 9,000 Btu models; add 40 watts for size 12 and 70 watts for size 15.
  • Page 16: Dimension And Weights

    Dimension and Weights Unit with Wall Sleeve and Subbase Accessory Top View Front View Right Side View Notes: 1. Allow a minimum of 3 ” clearance between cabinet and floor to permit installation of options subbase. 2. Allow minimum of 3” clearance between cabinet and side walls to permit front panel removal. 3.
  • Page 17 Dimension and Weights Field Supplied Extension PTAC-PRC001-EN...
  • Page 18 Dimension and Weights Hydronic Heat Kit NOTE: Wall sleeve must extend exactly 3 inches from finished interior wall Notes: 1. This kit completely encloses all plumbing and coils, but still allows easy access to controls. 2. The chassis can slide out for easy service without removing hydronic plumbing. 3.
  • Page 19 Dimension and Weights Duct Package When two adjacent rooms need to be conditioned, a main duct kit and a duct extension kit are possible options. These kits transfer air from one room to another, yet allow different air flows for the rooms (airflow distribution can be adjusted from 65/45 to 80/20.) Front View Duct Termination Kit...
  • Page 20: Mechanical Specifications

    Mechanical Specifications Unit Chassis Condenser/Evaporator Fans Outside Air Damper/Vent Control Each unit will be slide-out design shipped One direct drive with a permanent split The vent control will allow 65 to 70 cfm with room cabinet front installed. Unit capacitor two-speed motor. The of fresh air to be drawn into the room.
  • Page 21 Mechanical Specifications Unit Controls Load Shedding Terminals The unit controls will be full solid-state The LS/IN terminals will provide a and accessible from the top. The connection for a switch that can be standard unit mounted controls will added to close the circuit and lockout the include two rotary (switch) knobs compressor and electric heat when the controlling unit operational and...
  • Page 22: Options

    Duct Transition and Extended Kit This temperature sensor overrides grille is not made by Trane. These baffles A main duct transition piece will attach to standard unit mounted sensor to allow are required to deflect discharge air...
  • Page 23 The installation of Trane’s security key The circuit breaker kit, available in 15, 20, locks helps prevent tampering of the 25 or 30 amp, can be used with Trane’s controls used to set temperature, subbases. It gives overcurrent protection heating and cooling functions. Locks are and its location allows turning unit on or available for all PTAC models.
  • Page 24: Warranty

    Warranty Warranty Information Standard Warranty •Full First-Year Warranty Trane will repair or replace, free of charge including labor, any part which proves to be defective due to workmanship or materials. •Full Five-Year Sealed System Warranty Trane will repair or replace, free of...
  • Page 25 For more information contact your local distributor (dealer), local district office, or Since The Trane Company has a policy of continuous product and product data improvement, it reserves the e-mail us at comfort@trane.com right to change design and specifications without notice.