Job Name:
Drawing Reference:
System No.:
GENERAL FEATURES
• R410A refrigerant
• Seven sizes from 6,000 to 30,000 Btu/h
• Powerful airflow (CFM)
• Compact, lightweight, shiny-white, flat-panel design
• Quiet operation
• Multiple fan-speed settings
• Intake grille filter is easily removed for cleaning
• Built-in receiver is standard
• IT Terminal plug
SPECIFICATIONS
Capacity*
Cooling........................................................8,000 Btu/h
Heating........................................................9,000 Btu/h
Power
Power Source............................208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling.............................................................0.03 kW
Heating.............................................................0.03 kW
Current
Cooling........................................................................0.30 A
Heating........................................................................0.30 A
Minimum Circuit Ampacity (MCA).................................0.38 A
Maximum Overcurrent Protection (MOCP) Fuse.................15 A
External Finish...............................Munsell No. 1.0Y 9.2 / 0.2
External Dimensions
Inches.................................11-5/8 H x 35-3/8 W x 9-13/16 D
mm..............................................295 H x 989 W x 249 D
Notes:
PKFY-P08NHMU-E2
Model:
Location:
Schedule No.
Date:
Net Weight
Unit...........................................................29 lbs. / 13 kg
Coil Type.................................................................Cross Fin
Fan
Type x Quantity...................................Line Flow Fan x 1
Airflow Rate (Low-Mid1-High)......................320 - 370 - 423 CFM
Motor
Type....................................One-phase Induction Motor
Output...........................................................0.030 kW
Air Filter....................................Polypropylene Honeycomb
Refrigerant Piping Dimensions
Liquid (High Pressure).....................1/4" / 6.35 mm (Flare)
Gas (Low Pressure).......................1/2" / 12.7 mm (Flare)
Drainpipe Dimension..................................I.D. 5/8" / 16 mm
Sound Pressure Levels
Low-Mid1-Mid2-High.............................34 - 39 - 43 dB(A)
OPTIONS
□ External Heat Adapter................................PAC-YU25HT
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
(35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB
Note: Ventilation air: Providing sufficient ventilation air is an impor-
tant part of every building design. ASHRAE Standard 62 provides
the minimum ventilation air requirement. Also, check local codes.
(Aluminum Plate Fin and Copper Tube)