Eaton Powerware 5130 User Manual page 68

Powerware series rack/tower ups 1000–3000 va
Hide thumbs Also See for Powerware 5130:
Table of Contents

Advertisement

TROUBLESHOOTING
Table 17. Troubleshooting Guide
Alarm or Condition
When starting the UPS with the
button, all the indicators turn on
once, the alarm beeps once, and
then
indicator remains on.

The
button,
and
indicators are on and all the
bar graph indicators flash.
The
button and
indicator
are on and all the
bar graph
indicators flash.
The
indicator is on and all the
bar graph indicators flash.
The
indicator alone is on and
the alarm sounds continuously.
62
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide
www.eaton.com/powerquality
Possible Cause
The remote power-off (RPO)
contact has been activated to
shut down the UPS and now
prevents restart.
The percent load is greater than
the set overload level or UPS
capacity.
A critical overload has occurred.
If utility power fails, the load will
not be protected in Battery
mode.
A battery fault has been
detected during the automatic
test.
UPS fault condition. The load is
not supplied.
Action
Set the contact back to its normal position
and press the
button to restart.
Check the power drawn by the connected
devices and disconnect any non-priority
devices. Check the overload setting.
Check the power drawn by the connected
devices and disconnect any non-priority
devices.
Replace the battery (see "Replacing
Batteries" on page 48).
Contact your service representative.