Greenheck CSP-B Installation, Operation And Maintenance Manual

Greenheck CSP-B Installation, Operation And Maintenance Manual

Greenheck fan corp. ceiling exhaust and inline fans installation, operation and maintenance manual sp-b, csp-b

Advertisement

Quick Links

READ AND SAVE THESE INSTRUCTIONS

®
Installation, Operation and Maintenance Manual
Fig. 1
WARNING !
To reduce the risk of fire, electric shock, or injury to
persons, observe the following:
• Suitable for use with solid-state speed controls.
• Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
• Before servicing or cleaning unit, switch power off at
service panel and lock service disconnecting means to
prevent power from being switched on accidentally.
When the service disconnecting means cannot be
locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
• Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction.
• Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent back drafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) and the local code authorities.
• When cutting or drilling into wall or ceiling, do not
damage electrical wiring or other hidden utilities.
• Acceptable for use over a bathtub or shower when
installed in a GFCI protected branch circuit. (Up
through size SP-A390)
• Never place a switch where it can be reached from a
tub or shower.
• Ducted fans must always be vented to the outdoors.
• These fans are not recommended for cooking exhaust
applications. They are designed primarily for low
temperature, clean air applications only. The diagram
shows the minimum distance these fans should be
placed in relation to cooking equipment.
• Fan/Light combination not to be installed in a ceiling
thermally insulated to a value greater than R40.
CAUTION !
• For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
Prepare the Fan
1. If power assembly (motor and wheel) is not installed in housing, insert
the electrical plug into fan socket, then slide wheel end of power
assembly into fan housing and rotate clockwise until it is positioned
under tabs. Align the holes and attach by using two sheet metal
screws provided, shown in Fig. 1.
Ceiling Radiation Damper - CRD
1. If fan is to be used in a fire resistive membrane ceiling, a ceiling
radiation damper must be used. Otherwise proceede to Install the
Fan.
2. If the ceiling radiation damper is already mounted to the fan from the factory,
proceed to Install the Fan.
3. To mount the ceiling radiation damper to fan, make sure grille
Install the Fan
1. For best performance, choose a
2. Attach adjustable mounting brackets to
Fig. 6
Model SP-B
Model CSP-B
Ceiling Exhaust and Inline Fans
attachment tabs are facing down. Then place the inlet part of the
fan into the ceiling radiation damper collar, and use self-tapping
1
sheet metal screws #10x
/
in. (by
2
others) to screw through the damper
collar and into the fan housing, shown in
Fig. 2. If the fan/light combination is being
used, make sure ceiling radiation damper
has an electrical plug in it. The electrical
plug must be inserted into the fan. Make
sure the electrical wire will not interfere with
damper operation, shown in Fig. 3.
location with the shortest possible duct
run and minimum number of elbows. Do
not mount near cooking equipment, shown
in Fig. 4.
fan, but leave the screws loose until
proper height is determined, shown in
Fig. 5. For fan and fan/light combination
1
3
opening, cut a 14
by 11
inch hole in
8
4
the ceiling. For fan/CRD combination
3
1
opening, cut a 14
by 12
inch hole in the
8
4
ceiling.
For Frame Construction: Position unit
2. Tighten
between joists. Position brackets such
Fan
that bottom edge of housing will be flush
Ceiling
with finished ceiling, and tighten the
adjustable
1. Adjust to be flush
mounting brackets,
with finished ceiling
shown in Fig. 6.
For Hanging Installations: Use Greenheck's
optional vibration isolator kit Part Number VI
Kit. Using the fan's standard adjustable
mounting brackets and 10 by 32 threaded
rod (by others) hang unit as shown in Fig. 7.
PN 455480
Fig. 2
Attachment Tabs
Wires to ceiling fan
Fig. 3
Do not allow
interference in
this area
Wires from lighted grille
Do not install
fan in this area
45º
45º
Fig. 4
Brackets can be
arranged to adapt
to most mounting
conditions
Fig. 5
Fig. 7

Advertisement

loading

Summary of Contents for Greenheck CSP-B

  • Page 1: Read And Save These Instructions

    Kit. Using the fan’s standard adjustable mounting brackets and 10 by 32 threaded rod (by others) hang unit as shown in Fig. 7. Model SP-B Model CSP-B Ceiling Exhaust and Inline Fans Fig. 2 in. (by Wires to ceiling fan...
  • Page 2: Installation Recommendations

    Green wire is “Ground” 220 - 240 Volt Black wire is “Hot” White wire is “Hot” Green wire is “Neutral/Ground” Fig. 11 Squeeze tabs to insert/remove lens SP-B & CSP-B IOM FS Rev 8 March 2004 Copyright © 2004 Greenheck Fan Corp.