Installation, Operation and Maintenance Instructions
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F.
SAFEty WARNING:
Improper installation, adjustment, alteration,
service or maintenance can cause property damage,
injury or death. Read the installation, operating,
and maintenance instructions thoroughly before
installing or servicing this equipment.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
FSDR-XXX, SEFSDR-XXX,
AND SSFSDR-XXX MODELS
1
Hour Fire & Combination Fire
1
2
FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model
Dampers are intended for installation in accordance with
combination fire smoke damper requirements established
by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B & 101
BOCA National Building Codes
ICBO Uniform Building Codes
IBC International Building Codes
SBCCI Standard Building Codes
New york City (MEA listing #260-91-M)
"UL CLASSIFIED (see complete marking on product)"
"UL CLASSIFIED to Canadian safety standards (see
complete marking on product)"
UL Standard 555 & 555S (Classification #R13317)
WARRANty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
This manual is the property of the owner, and is required
for future maintenance. Please leave it with the owner
when the job is complete.
Part #461868
Smoke Dampers
Vertical and Horizontal Mount

Advertisement

loading

Summary of Contents for Greenheck FSDR-XXX

  • Page 1 AND SSFSDR-XXX MODELS ⁄ Hour Fire & Combination Fire Vertical and Horizontal Mount FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model Dampers are intended for installation in accordance with combination fire smoke damper requirements established National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B & 101...
  • Page 2: Table Of Contents

    Securing the Damper Assembly to Wall and Floor Openings • Actuator Connections • Connection and Operation of Temperature Control Devices • FSDR-XXX and DFDR-XXX Blade Orientation • Recommended Preparation of Openings in Wood and Metal Stud Walls Maintenance ...7 Troubleshooting ...7 Pre-Installation Guidelines The basic intent of a proper installation is to secure the fire smoke or fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation.
  • Page 3: Electrical Guidelines

    Electrical Guidelines All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of SAFEty DANGER ! : to avoid causing death or serious bodily harm to building occupants, follow all instructions carefully.
  • Page 4: Sleeve Length And Wall Thickness

    Insert the damper assembly into the prepared opening, to appropriate depth (see Page 3, Fig. 1). Recommended maximum and minimum insertion depth can be exceeded if: the operation of the damper actuator is not impeded and the C L of the damper blade remains within the plane of the wall/floor IMPORtANt SAFEty DANGER! : To avoid causing death or serious bodily harm to building...
  • Page 5: Actuator Connections

    5. ACtUAtOR CONNECtIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines). 6. CONNECtION AND OPERAtION OF tEMPERAtURE RESPONSE DEVICES (Fusible Link, RRL OPtION, OCI OPtION, tOR OPtION, and PRV OPtION) RRL - Dampers will be supplied with a fusible link...
  • Page 6: Fsdr-Xxx And Dfdr-Xxx Blade Orientation

    Fig. 6 FSDR-XXX and DFDR-XXX Blade Orientation Axle 30° Off Horizontal (Maximum) 8. Recommended Preparation of Openings in Wood and Metal Stud Walls • Frame wall openings as shown. (see Fig. 7) • Double vertical studs are not required for openings 36 in.
  • Page 7: Maintenance

    Push reset button located on backside of RRL or TOR. Disconnect linkage from jackshaft, open damper, power actuator to end of spring, tighten linkage. Verify amp draw. Replace link Copyright © 2006 Greenheck Fan Corporation 461868 FSDR-XXX Rev. 7 March 2006...