Drolet HT-1600 Owner's Manual page 16

Epa woodstoves
Table of Contents

Advertisement

Floor protector
If the stove is to be installed on top of a combustible floor, it must be guarded by a non
combustible material as shown on figure 1.3 (see the dotted line area).
G
H
I
J
M
N
*Steel with a minimum thickness of 0.015'' (0.38 mm) or ceramic tiles sealed together
with grout. No protection is required if the unit is installed on a non-combustible floor (ex:
concrete).
Note 1 : The floor protection at the back of the stove is limited to the stove's required
clearance if such clearance is smaller than 8 inches (205 mm).
Note 2 : Only required under the horizontal section of the connector. Must exceed
each side of the connector by at least 2 inches (51 mm).
Reduced clearances using shielding
You may decrease the clearances by installing heat radiation shields between the walls or
the ceiling and the stove. These heat radiation shields must be installed permanently, and
can include sheet metal, a rigid non-combustible sheet or a masonry wall.
Clearances of not less than 1" (25 mm) and not more than 3" (76 mm) between the bottom
of the shield and the floor and not less than 3" (76 mm) between the top of the shield and
the ceiling must be respected to allow vertical air circulation behind the shield. The shield
must extend 20" (500 mm) above the stove top and 18" (450mm) to each side of the stove
(see graphic 1).
FLOOR PROTECTOR*
CANADA
8'' (205 mm) – Note 1
8'' (205 mm)
18'' (460 mm)
From door opening
N/A (USA only)
8'' (205 mm)
N/A (USA only)
USA
N/A (Canada only)
N/A (Canada only)
16'' (410 mm)
From door opening
8'' (205 mm)
N/A (Canada only)
Note 2
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Epa ht-2000Ht1200Ht-200075281Epa ht-1600

Table of Contents