Ensure that the total power requirement of the equipment to be protected does not exceed the rated
output power of the UPS. (output power for your unit is indicated on the rating label on the rear panel).
When using the 120V split phase outputs make sure that the load per 120V output does not exceed half
the rating.
The UPS may only be installed by trained personnel. The UPS must be grounded when in use: Connect
the UPS to a single phase, three wire AC source equipped with an earth connection.
Use insulated copper input and output wiring, rated 90°C derated to 40°C, wire size based on the
ampacities given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993.
This wiring shall have the following minimum sizes:
INPUT WIRING:
UPS model
LP 5-11U
LP 6-11U
LP 8-11U
LP 10-11U
Table 2. Input wiring
OUTPUT WIRING:
UPS model
LP 5-11U
LP 6-11U
LP 8-11U
LP 10-11U
Table 3. Output wiring
TIGHTENING TORQUE FORCE:
UPS model
LP 5/6-11U/120V
All other models
Table 4. Tightening torque force
LX: OPM_LPU_11U_5K0_10K_1US_V030
Utility voltage
120V
208V
6 AWG
10 AWG
4 AWG
8 AWG
N/A
6 AWG
N/A
4 AWG
Output voltage
120V
208V
8 AWG
10 AWG
8 AWG
10 AWG
6 AWG
8 AWG
4 AWG
8 AWG
Tightening torque force
22 Lbs/inch
18-20 Lbs/inch
Digital Energy
240V
10 AWG
10 AWG
8 AWG
6 AWG
240V
10 AWG
10 AWG
8 AWG
8 AWG
10