Battery Care And Storage Guidelines; Ups Battery Replacement Procedure - HP R1500 - UPS XR User Manual

Hp r1500 g3 ups user guide
Table of Contents

Advertisement

NOTE:

Battery care and storage guidelines

CAUTION:
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep these
batteries charged while in storage is implemented.
To maintain the batteries:
Minimize the amount of time the UPS uses battery power by matching the UPS configuration with the
utility voltage. See "Selecting the UPS voltage configuration (on page 14)."
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of
the UPS regularly with a vacuum cleaner.
Maintain the ambient temperature at 25°C (77°F).
If storing a UPS for an extended period, recharge the batteries every 6 months, and then update the
battery recharge date label.

UPS battery replacement procedure

This component is hot-swappable and can be replaced without powering down the UPS.
(optional) To replace the component with the UPS powered down, refer to "Powering down the UPS (on
1.
page 21)."
Remove the UPS front bezel
2.
Disconnect the battery leads.
3.
Replace all battery modules at the same time.
Because of the short shelf life of the batteries, avoid storing a battery spare as a
("Removing the UPS front
bezel" on page 22).
Maintenance 23