FIREWOLF FW2-H Installation Instructions

Smoke detectors

Advertisement

These installation instructions are for the FW-4, FW4-H, FW-2 and the FW2-H FIREWOLF Smoke Detectors.
CAUTION!!!
Install this and all life safety devices in accordance with
applicable NFPA standards, local codes, and the au-
thorities having jurisdiction. Failure to follow these in-
structions may result in failure of the detector to initiate
an alarm condition. Napco Security Systems, Inc. and
the original equipment manufacturer, are not responsi-
ble for detectors that have been improperly installed,
tested, or maintained.
For testing and cleaning information, refer to these in-
structions and/or call the NAPCO fax request line at
(631) 842-3291. Also refer to NFPA-72 Chapter 5 for
Automatic Fire Detectors for installation guidelines and
Chapter 7 for testing and maintenance requirements.
Use "3M" Weatherban # 606 non-flammable sealing
compound to seal field wiring conduit openings in the
mounting back box. Compliance with this request may
reduce the occurrence of the "STACK EFFECT".
Box Mounting
Trim Ring
3" OCT
Wiring
: Connect wiring to the bases as shown in the wiring diagrams that follow. Detectors may be mixed on the same initiating
loop as long as the number of two-wire powered detectors does not exceed the specifications of the control panel. See Specification
Table above.
CAUTION: Connect wiring to terminals as shown. Do not loop wire under terminals. Break wire run to provide supervision.
FW-4 Wiring Diagram
FW-2 Wiring Diagram
Compatible Control Panels:
FW-C2Z, FW-C4Z, FW-C4EZ
GEM-P3200
GEM-P9600
GEM-P800, GEM-P801
GEM-P816, GEM-P1632
NAPCO Express XP600
MA3000
Note: For cross listings with additional manufacturers and models pending,
contact the NAPCO Technical Support Department for the latest listings at
(800) 645-9440. Also available online at www.napcosecurity.com (go to the
Firewolf folder and download FW2_WI1009_ADDM).
®
Magnum Alert
is a Registered trademark of NAPCO. Gemini,
Napco Security Systems, Inc.
333 Bayview Avenue * Amityville, NY 11701
Phone: (800) 645-9445 (631) 842-9400 Fax: (631) 789-3383
®
R
4" Oct
U.L. Listed
Control
Panel
U.L. Listed
Power
Supply
*24VDC
U.L. Listed
Power
Supply
*12VDC
* = Use 12 or 24VDC - CANNOT BE USED SIMULTANEOUSLY
U.L. LISTED
COMPATIBLE
CONTROL PANEL

INSTALLATION INSTRUCTIONS

FW4-H and FW2-H
SPECIFICATIONS
FW-2
Detector
Type of Detector
Photoelectric
(2 wire baseless)
Working Voltage
8.0 - 35.0 VDC
Voltage
Filtered DC
15% ripple max.
Waveform
Limit current to
Max. Alarm
150mA @ 35.0
Current
VDC
Max. Surge
200µA
Current
38µA @ 12 VDC
Average
55µA @ 24 VDC
Standby Current
70µA @ 35 VDC
Compatibility
HD-6
Identifier
Sensitivity Test
Built-In Test
Feature
Feature
See Wiring
NAPCO
Diagram Below
Control Panel
Compatibility
Heat Element
N/A
Rating
Note: When mounting detector on a wall, it must be between 4" and 12" from the ceiling.
The FW-2 requires current
Limiting to no more than 150mA
Signature
and NAPCO Express
SMOKE DETECTOR DATA
FW2-H
FW-4
Photoelectric
Photoelectric
(2 wire baseless)
(4 wire baseless)
8.0 - 35.0 VDC
8.0 - 35.0 VDC
Filtered DC
Filtered DC
15% ripple max.
15% ripple max.
Limit current to
55mA @ 35.0
150mA @ 35.0
VDC
VDC
200µA
200µA
38µA @ 12 VDC
38µA @ 12 VDC
55µA @ 24 VDC
55µA @ 24 VDC
70µA @ 35 VDC
70µA @ 35 VDC
HD-6
N/A
Built-In Test
Built-In Test
Feature
Feature
See Wiring
N/A
Diagram Below
135° F
N/A
CAUTION
@ 35.0 VDC
are Trademarks of NAPCO.
FW4-H
Photoelectric
(4 wire baseless)
8.0 - 35.0 VDC
Filtered DC
15% ripple max.
55 mA @ 35.0
VDC
200µA
38µA @ 12 VDC
55µA @ 24 VDC
70µA @ 35 VDC
N/A
Built-In Test
Feature
N/A
135° F
LISTED
END-OF-LINE
DEVICE
LISTED
END-OF-LINE
RELAY
12 OR 24VDC
LISTED
END-OF-LINE
DEVICE

Advertisement

loading

Summary of Contents for FIREWOLF FW2-H

  • Page 1: Installation Instructions

    INSTALLATION INSTRUCTIONS FW4-H and FW2-H These installation instructions are for the FW-4, FW4-H, FW-2 and the FW2-H FIREWOLF Smoke Detectors. SPECIFICATIONS SMOKE DETECTOR DATA CAUTION!!! Install this and all life safety devices in accordance with FW-2 FW2-H FW-4 FW4-H Detector...
  • Page 2: Mounting

    The detector should be re-tested by performing the test procedure described in this document. Note: If after testing, the detector is not working within the prescribed limits, then return it to the manufacturer for servicing. WI 972C 10/04 © NAPCO 2004...

This manual is also suitable for:

Fw-4Fw4-hFw-2Fw-4Fw4-hFw-2