Solid Core and Split Core 4-20 mA
Output Current Sensors
CTS-20; CTP-20
SAFETY
WARNING
For CTS-20 Series current sensors, ensure
that all power sources are disconnected and
locked out before installation as severe injury
or death may result from electrical shock due
to contact with high voltage wires.
CAUTION
This product is not intended to be used for life
or safety applications.
CAUTION
This product is not intended for use in any
hazardous or classified locations.
INSTALLATION
Make sure that all installations are in compliance with all
national and local electrical codes. Only qualified
individuals that are familiar with codes, standards, and
proper safety procedures for high-voltage installations
should attempt installation. The current sensor is a 2-
wire, 4 to 20 mA Loop Powered device that requires a
regulated +12 to 30 Vdc external power source.
IMPORTANT
The current switch should be used on insulated
conductors only!
The current sensors may be mounted in any position
using the two (2) #8 x 3/4 in (19 mm) Tek screws and the
mounting holes in the base or snapped directly on to the
1-3/8 in. (35 mm) DIN rail (See Figures 3 and 4). Leave a
minimum distance of 1 in. (25 mm) between the current
sensor and any other magnetic devices such as
contactors and transformers.
INSTALLATION INSTRUCTIONS
3X
Fig. 1. Sensor placed on DIN rail
3X
Fig. 2. Sensor removed from DIN rail
IND.CONT.EQ.
3JHX
M25289
M25290
62-0245—01

Advertisement

loading

Summary of Contents for Honeywell CTP-20

  • Page 1 Solid Core and Split Core 4-20 mA Output Current Sensors CTS-20; CTP-20 INSTALLATION INSTRUCTIONS SAFETY WARNING For CTS-20 Series current sensors, ensure that all power sources are disconnected and locked out before installation as severe injury or death may result from electrical shock due to contact with high voltage wires.
  • Page 2 Fig. 3. Current transformer M25298 Fig. 4. Opening sensor by hand Wiring Honeywell recommends the use of 16 to 22 AWG (1.3 to 0.3 mm ) shielded cable, copper wire only for all current sensor applications. A maximum wire length of less than 98.4 feet (30 meters) should be used between the current...
  • Page 3 160 Amps 200 Amps CTS-20-250-VFD-001 0-200 Amps Middle 320 Amps 400 Amps 0-250 Amps High 400 Amps 500 Amps CTP-20-005-AVG-001 Split 4-20 mA Average 0-5 Amps Fixed None 100 Amps 125 Amps CTP-20-050-AVG-001 Split 4-20 mA Average 0-10 Amps 100 Amps...
  • Page 4: Troubleshooting

    20 mA = 250 Amps Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2007 Honeywell International Inc. 62-0245—01 C.H. Rev. 06-07...