Oil Burner Mounted Electric Fan Timer
APPLICATION
The ST7997 Oil Burner Mounted Electric Fan Timer
integrates control of burner and circulator fan operations in
an oil furnace and is the central wiring point for most
electrical components in the furnace. The ST7997 mounts
on a standard four-inch by four-inch junction box typically
located on the oil burner. When used with the R7997
Integrated Oil Primary Controller and Ignitor, it provides
simplified wiring and field serviceability. The basic
purposes of the ST7997 are to monitor the thermostat for
heat, cool and fan demands, run the oil burner primary
control and run a two-speed circulating fan, as required.
The ST7997 also monitors a limit switch string that
energizes the circulating fan when the limit switch opens.
The ST7997 provides electronic air cleaner (EAC) and
humidifier (HUM) terminal connections for field installation
convenience.

SPECIFICATIONS

Electrical
Input Ratings
Supply Voltage:
102 to 132 Vac (120 Vac nominal), 60 Hz.
Supply Current:
100 mA maximum without loads connected to outputs.
20A maximum with loads connected to outputs.
Output Ratings:
Relay Contacts:
Circulator Heat or Cool Blower Speed Rating: 15A Full
Load Amperage (FLA) (0.75 pF)/30A Locked Rotor
Amperage (LRA) (0.5 pF).
NOTE: FLA rating is reduced by EAC load.
EAC:
1A maximum.
Circulator Continuous Blower Speed Rating:
8A FLA (0.75pF)/16A LRA (0.5pF).
Humidifier:
1A maximum.
Molex® is a registered trademark of Molex Incorporated.
Copyright © 1998 Honeywell Inc. • All Rights Reserved
INSTALLATION INSTRUCTIONS
Limit:
10A maximum.
L1/L2 (Burner):
20A maximum.
Thermostat Current:
Heat Mode: 100 mA (R7997 supplied).
Cool Mode: Cooling contactor load 500 mA maximum
(ST7997 supplied).
Cooling Contactor:
2 VA minimum, 12 VA maximum.
Molex® is a registered trademark of Molex Incorporated.
Fuse:
1A (automotive type ATO).
Delay Timings:
Heat On Delay: 45 or 60 seconds (fixed or field
selectable via DIP switch optional position 3).
Heat Off Delay: 60/100/120/150 seconds (four field
selections via DIP switch positions 1 and 2).
Cool On/Off Delay: 0/0 or 30/30 seconds (fixed).
Delay Timing Tolerances:
5 seconds or 20 percent, whichever is greater.
Environmental
Temperature Ranges:
Operating: -40 F (-40 C) to +150 F (66 C).
Storage: -20 F (-29 C) to +150 F (66 C).
Humidity:
90 percent relative humidity at 95 F (35 C),
noncondensing.
Approvals:
Underwriters Laboratories Inc. Component
Recognized: File 353.
Canadian Underwriters Laboratories inc. Component
Recognized: Pending approval.
Mechanical:
Dimensions (Fig. 1):
4-9/32 in. (109 mm) long by 4-1/4 in. (108 mm) wide by
3-27/32 (97 mm) high. See Fig. 1.
X-XX UL
ST7997
69-1204

Advertisement

loading

Summary of Contents for Honeywell ST7997

  • Page 1: Specifications

    Integrated Oil Primary Controller and Ignitor, it provides (ST7997 supplied). simplified wiring and field serviceability. The basic purposes of the ST7997 are to monitor the thermostat for Cooling Contactor: heat, cool and fan demands, run the oil burner primary 2 VA minimum, 12 VA maximum.
  • Page 2: Location And Mounting

    Location and Mounting Y G Rc Mount the ST7997 on the oil burner 4 in. (102 mm) by 4 in. 4-9/32 (109) (102 mm) junction box compartment using four No. 6 screws (obtained locally). See Fig. 2.
  • Page 3 OIL PRIMARY WITHOUT BLOWER DELAY HEAT CALL LIMIT THERMOSTAT 5-WIRE CONTROL ISOLATION ELECTRONICS OEFT ST7997 COMPRESSOR CONTACTOR J-BOX SCREW TERMINAL BURNER 1/4 IN. QUICK CONNECT MOTOR M12924 Fig. 3. ST7997 Oil Burner Mounted Electronic Fan Timer standard wiring connections. 69-1204...
  • Page 4: Wiring Options

    VALVE MOTOR 1/4 IN. QUICK CONNECT M12922 Fig. 4. ST7997 Oil Burner Mounted Electronic Fan Timer wiring for units with pre- and post purge. NOTE: Two dummy quick connect terminals, labeled Wiring Options “unused wires”, not connected to the ST7997 circuitry, are provided on the back of the case to Wiring options are listed in Table 1.
  • Page 5 1/4 IN. QUICK CONNECT POWER BURNER VENT MOTOR MOTOR M12923 Fig. 5. ST7997 Oil Burner Mounted Electronic Fan Timer airflow switch and power vent motor for power venting wiring. Table 1. ST7997 Wiring Options. Mode Action System Response Constant circulating fan is...
  • Page 6 Troubleshoot by checking for appropriate voltages at the ST7997 terminals controlling the burner motor and heat and cool circulating fan. The ST7997 schematic (Fig. 3) shows internal switching to clarify operation and assist in troubleshooting. Table 2 provides the ST7997 operating sequence.
  • Page 7 Heat fan-off delay timing begins. When timing is completed, the circulating fan is de-energized. ST7997 returns to standby mode (oil primary control and circulating fan are off, unless continuous fan operation is selected at the thermostat). Burner fails to light.
  • Page 8 ST7997 OIL BURNER MOUNTED ELECTRIC FAN TIMER Home and Building Control Home and Building Control Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7 www.honeywell.com 69-1204 69-1204 G.R. 8-98...