Duct-mount and outdoor-mount humidity/temperature sensors

Advertisement

H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
CHECKOUT
CAUTION
Equipment Damage Hazard.
Can short electric circuitry.
• Never connect 120 Vac to the transducer.
• Connect only DC voltage to a transducer
intended for DC supply.
NOTE: Use laboratory quality meters and gauges for
applications requiring a high degree of accuracy.
1. Verify the transducer is mounted in the correct posi-
tion.
2. Verify appropriate input signal and voltage supply.
3. Verify appropriate configuration range.
Problem
No reading
• Verify correct supply voltage at the power terminal blocks.
• Verify correct wiring configuration and DIP switch settings.
• Verify that terminal screws are connected tightly with all wires firmly in place.
Erratic readings
• Verify all wires are terminated properly.
• Ensure that there is no condensation on the board.
• Verify clean input power. In areas of high RF interference or noise, shielded cable can be
Table 2. Troubleshooting.
necessary to stabilize signal.
Converting Output Signal to Percent RH
4 to 20mA Signal
signal [in mA] 4
------------------------------------------------ -
=
percent RH
0.16
Example: 12 mA output signal
(12 - 4)/ 0.16 = 50% RH
0 to 10 Vdc Signal
Example: 8 VDC transmitter signal output
8 Vdc/0.10 = 80% RH
Items to Check
5
63-2579—3