Generac Power Systems GTS Series Specification page 2

Gts series 100 - 400 amps, 600 vac automatic transfer switches

Advertisement

GTS Control Systems
2 of 2
Withstand Current - 600 Volt GTS Series
GTS Rated Amps
FUSE PROTECTED
Maximum RMS Symmetrical
Fault Current – Amps
Maximum Fuse
Size – Amps
Fuse Class
CiRCUiT BREAkER PROTECTED (See separate sheet for specific circuit breakers)
Maximum RMS Symmetrical
Fault Current – Amps
Protective Device Continuous
Rating (Max) – Amps
• Tested in accordance with the withstand and closing requirements of UL 1008 and CSA Standards
• Current ratings are listed @ 480 VAC
Terminal Lug Wire Ranges
GTS RATED
AMPS
100
150
200
300
400
* Not included in GTS with switched neutral. ** Allowable wire range in brackets is for 2 wires per lug.
Utility Voltage
Dropout ........................................................................................................................75-95% (Adj.)
Pickup ..........................................................................................................................85-95% (Adj.)
Line Interrupt ..........................................................................................................0.1-10 Sec. (Adj.)
Engine Minimum Run ........................................................................................................... 5-30 Min. (Adj.)
Engine Warmup.............................................................................................................. 5 Sec.-3 Min. (Adj.)
Return to Utility .................................................................................................................... 1-30 Min. (Adj.)
Engine Cooldown ................................................................................................................. 1-30 Min. (Adj.)
Standby Voltage ......................................................................................................................85-95% (Adj.)
Standby Frequency..................................................................................................................80-90% (Adj.)
Time Delay Neutral ............................................................................................................0.1-10 Sec. (Adj.)
Transfer on Exercise . ............................................................................................................... On/Off Switch
Warmup Timer Bypass . ........................................................................................................... On/Off Switch
Time Delay Neutral Bypass . ..................................................................................................... On/Off Switch
Inphase Monitor ...................................................................................................................... On/Off Switch
100
200,000
200
J,T
14,000
150
Unit Dimensions
GTS
Rated
Amps
100
150-200 120/240
150-200 120/208
150-200 277/480
150-200
300-400 120/240
300-400 120/208
300-400 277/480
300-400
* Note: On NEMA 1 enclosures only, door overlaps enclosure – door dimensions are 48.8 H X 30.8 W. All dimensions in inches.
CONTACTOR TERMiNALS
(1 LUG PER POLE)
LUG WiRE RANGE
2/0 – 14 AWG
400MCM – 4 AWG
400MCM – 4 AWG
600MCM – 4 AWG
or 2 – [250MCM – 1/0 AWG]
600MCM – 4 AWG
or 2 – [250MCM – 1/0 AWG]
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2010 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 094700000S-A / Printed in U.S.A. 01/06/11
LOGIC CONTROL w / Inphase Monitor
150
200
200,000
200,000
400
400
J,T
J,T
25,000
25,000
300
300
Enclosure Enclosure Wall Mount Enclsoure Weight
Voltage
Height
Width
H
W
All
36
24
36
24
36
24
48*
30*
600
48*
30*
36
24
36
24
48*
30*
600
48*
30*
NEUTRAL BAR*
# LUGS
LUG WiRE RANGE
4
2/0 – 14 AWG
4
350MCM – 6 AWG
4
350MCM – 6 AWG
4
600MCM – 4 AWG
[250MCM – 1/0 AWG]**
4
600MCM – 4 AWG
[250MCM – 1/0 AWG]**
300
400
200,000
200,000
600
600
J,T
J,T
35,000
35,000
600
600
Bolt Pattern
Depth
(lbs.)
M1
M2
D1
D2
18
37.5
12.7
10
180
18
37.5
12.7
10
185
18
37.5
12.7
10
185
24
49.5
14.8
12
265
24
49.5
14.8
12
265
18
37.5
12.7
10
245
18
37.5
12.7
10
245
24
49.5
14.8
12
325
24
49.5
14.8
12
325
GROUND LUG
(1 PROVIDED)
LUG WiRE RANGE
2/0 – 14 AWG
350MCM – 6 AWG
350MCM – 6 AWG
350MCM – 6 AWG
350MCM – 6 AWG
350MCM – 6 AWG