Installation and Operating Instructions
MANUAL TRANSFER SWITCH - MODELS 6379 AND 6381
NOTE TO INSTALLER: Please leave this guide with the consumer for future reference. READ THIS MANUAL IN ITS ENTIRETY BEFORE ATTEMPTING TO INSTALL THIS EQUIPMENT.
WARNING: Generac
®
transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators. Generac
accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. This transfer switch is intended for surface mounting OUTDOORS only. Our transfer
switches are UL listed to UL 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems. CAUTION: If using the generator and transfer switch for
larger appliances, such as electric water heaters, clothes dryers, electric ranges and small air conditioners, check the labels on the appliances to be sure they do NOT exceed the rating
of the generator. No appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch (20 or 30 amps). CALIFORNIA PROPOSITION 65
WARNING: Engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects and other reproductive harm. This product may contain or
emit chemicals known to cause cancer, birth defects and other reproductive harm.
What is Included in this Carton:
Manual Transfer Switch with wire harness, conduit, fittings and wire connectors
Installation Manual and Warranty Registration card
Tools and Items Needed for Installation:
¼" and 11/32 nut drivers
Straight blade and Phillips screwdriver
Electric drill
Wire cutter/stripper
Safety eye goggles
NEW 2-pole, 250 volt Breaker to mount in main load center – see specifications in Table I – manufactured by same as Main load center
Anchors and screws to mount transfer switch to wall
Compatible Circuit Breaker Types:
Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH, QAF (Arc Fault), QP (Surge Protector)
Cutler-Hammer Series BD, BR, BQ, GFC
Challenger Type A, C, HAGF
Square D Series HOM (Homeline)
GE Series THQL
Optional Items for Installation:
Arc-fault, GFCI or Surge protection circuit breakers. If Arc-fault, GFCI or Surge protection circuit breakers are used as the branch circuit protector in the main load
center, they MUST be used in the manual transfer switch. You may be able to re-use your existing AFCI, GFCI and Surge protection circuit breakers in the manual
transfer switch. See list of compatible breakers.
Power Cord to connect generator to transfer switch.
White, green, black and red THHN or MTW wire, 10 AWG, 300V rated (if breaker configuration is modified or expanded).
Switched Neutral Kit (SNK or Generac model 6297). If your portable generator has the neutral bonded to the frame of the generator AND 240V "full-power"
receptacle is GFCI protected, you will need to install a SNK accessory with your transfer switch to avoid nuisance tripping of the GFCI breaker on the generator.
NOTE ON NEUTRAL BONDED GENERATORS: Some portable generators are intended for use on jobsites and are subject to OSHA regulations for GFCI protection on all
receptacles. These "contractor grade" generators have their neutral wire bonded to the ground wire to pass OSHA inspection. When connected to a transfer switch this may
cause nuisance tripping of the generator GFCI breaker. When using a neutral bonded generator to power a house or building through a transfer switch consult the manufacturer of the generator (local
authorized service dealer) to determine if the neutral-ground bond wire on the generator can be removed without voiding the warranty. If it can be removed then no modifications to the transfer switch
installation are needed. If the neutral-ground bond cannot be removed, or voids the generator warranty, you MUST install a Switched Neutral Kit (SNK, Model 6297) accessory with your transfer
switch. NOTE: Removal of the neutral-ground bond should be performed only by an authorized generator service dealer or qualified electrician. If the neutral bond is removed the generator will no
longer pass OSHA inspection on job sites.
Thank you for purchasing a Generac Transfer Switch to safely connect a portable
generator to up to 16 circuits in your home or business (single phase only) for
standby power applications. This product is recommended for installations where
the main electrical panel is located outdoors. Product features include:
Generator Main and Utility Main are mechanically interlocked preventing utility and generator
from powering the circuits at the same time
Full branch circuit protection with Siemens
Pre-assembled wire harness for easy connection to the load center
Transfer switch can be expanded to up to 16 circuits using standard interchangeable type
circuit breakers.
Provision to accept GFCI, Arc Fault or Surge Protection circuit breakers to further protect your
home and electronic equipment (sold separately)
High Corrosion-resistant aluminum NEMA 3R enclosure
Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits.
Accepts a Switched Neutral Kit (Model 6297).
Power inlet provided for convenient cord connection from generator
1
®
circuit breakers
See Note on Neutral Bonded Generators below.

Advertisement

Table of Contents
loading

Summary of Contents for Generac Power Systems GenTran 6379

  • Page 1 White, green, black and red THHN or MTW wire, 10 AWG, 300V rated (if breaker configuration is modified or expanded). • Switched Neutral Kit (SNK or Generac model 6297). If your portable generator has the neutral bonded to the frame of the generator AND 240V “full-power” •...
  • Page 2: Step 1: Planning Your Installation

    4. The location of your load center/electrical panel in your home or business will determine where the transfer switch will be installed outdoors. TABLE 2 – CIRCUIT WORKSHEET CIRCUIT # MODEL 6379 MODEL 6381 APPLIANCE OR CIRCUIT STEP 2: INSTALLATION PROCEDURE: HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY.
  • Page 3: Wiring Diagram

    bottom of the manual transfer switch. The wire harness should enter the main load center in one of the bottom or lower side knockouts. A 1” or 1- 1/4” KO can be cut in the lower side of the enclosure if necessary. Remove the cover of the main load center and the transfer switch.
  • Page 4: Step 3: Using Your Transfer Switch

    Protected by US Patent No. US 6,861,596 B2 Generac Power Systems, Inc. Toll Free: 1-888-GENERAC www.generac.com 0196960SBY PN 50924 Rev A © 2012 Generac Power Systems, Inc. All Rights Reserved. GenTran and Generac are registered trademarks of Generac Power Systems, Inc.
  • Page 5 Fil blanc, vert, noir et rouge de THHN ou de MTW, 10 A.W.G., 300V (si la configuration du disjoncteur est modifiée ou augmentée. • Bloc neutre commuté (SNK ou modèle Generac 6297). Si le neutre de la génératrice portable est lié au cadre ET la prise de courant de 240V a une protection •...
  • Page 6: Étape 1 : Préparer L'installation

    4. L'emplacement du centre de distribution / du panneau électrique dans votre maison ou dans votre bureau détermine l'endroit à l'extérieur où sera installé le commutateur de transfert. TABLEAU 2 - FEUILLE DE TRAVAIL DU CIRCUIT No. du MODÈLE 6379 MODÈLE 6381 APPAREIL OU CIRCUIT circuit...
  • Page 7: Étape 2 : Procédure D'installation

    ÉTAPE 2 : PROCÉDURE D'INSTALLATION : LES BOÎTIERS DU COMMUTATEUR DE TRANSFERT CONTIENNENT DES TENSIONS DANGEREUSES QUI PEUVENT CAUSER LA MORT OU DES BLESSURES GRAVES. SUIVEZ LES PROCÉDURES D'INSTALLATION, DE FONCTIONNEMENT ET D'ENTRETIEN CORRECTES POUR ÉVITER LES TENSIONS DANGEREUSES. ARRÊTEZ LE DISJONCTEUR PRINCIPAL DU CENTRE DE DISTRIBUTION AVANT DE COMMENCER L'INSTALLATION.
  • Page 8: Diagramme De Câblage

    Generac Power Systems, Inc. Numéro gratuit : 1-888-GENERAC www.generac.com © Generac 2012 Power Systems, Inc. Tous droits réservés. GenTran et Generac sont des marques déposées de Generac Power Systems, Inc. PN 50924 Rév. A...
  • Page 9 Cable THHN o MTW blanco, verde, negro y rojo, 10 AWG, clasificado para 300V (si la configuración del disyuntor ha sido modificada o expandida). • Kit neutral con interruptor (SNK o Generac modelo 6297). Si su generador portátil tiene la unión neutral al marco del generador Y el receptáculo de 240V de •...
  • Page 10 4. La ubicación del centro de carga/panel eléctrico en su hogar o negocio determinará dónde se instalará el interruptor de transferencia en el exterior. TABLA 2: HOJA DE TRABAJO DE CIRCUITOS N.° DE MODELO 6379 MODELO 6381 APARATO O CIRCUITO...
  • Page 11: Paso 2: Procedimiento De Instalación

    PASO 2: PROCEDIMIENTO DE INSTALACIÓN: EXISTEN VOLTAJES PELIGROSOS DENTRO DE LAS CAJAS DEL INTERRUPTOR DE TRANSFERENCIA QUE PUEDEN CAUSAR LA MUERTE O DAÑOS PERSONALES GRAVES. SIGA LOS PROCEDIMIENTOS ADECUADOS DE INSTALACIÓN, USO Y MANTENIMIENTO PARA EVITAR LOS VOLTAJES PELIGROSOS. APAGUE EL DISYUNTOR PRINCIPAL EN EL CENTRO DE CARGA ANTES DE COMENZAR LA INSTALACIÓN.
  • Page 12: Diagrama Del Cableado

    III. DIAGRAMA DEL CABLEADO (se muestra el modelo 6381) ID DEL CIRCUITO PARA EL MODELO 6381 PASO 3: USAR EL INTERRUPTOR DE TRANSFERENCIA: NUNCA use generadores portátiles en interiores o en garajes, sótanos o cobertizos. Los generadores portátiles siempre deben usarse al menos a 5 pies de distancia de ventanas, puertas, conductos de ventilación o cualquier otra abertura.
  • Page 13 Protegido por la patente de los Estados Unidos N.° US 6,861,596 B2 Generac Power Systems, Inc. Línea gratuita: 1-888-GENERAC www.generac.com © 2012 Generac Power Systems, Inc. Todos los derechos reservados. GenTran y Generac son marcas registradas de Generac Power Systems, Inc 50924 Rev. A...

This manual is also suitable for:

Gentran 6381

Table of Contents