Installation and Operating Instructions
MANUAL TRANSFER SWITCH MODELS 6335 AND 6382
NOTE TO INSTALLER: Please leave this guide with the consumer for future reference. READ THIS MANUAL IN ITS ENTIRETY BEFORE ATTEMPTING TO INSTALL THIS EQUIPMENT.
®
WARNING: Generac
transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators. Generac
accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. This transfer switch is intended for surface mounting OUTDOORS. Our transfer
switches are UL listed to UL Standard 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems. CAUTION: If using the generator and transfer
switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges and small air conditioners, check the labels on the appliances to be sure they do NOT exceed
the rating of the generator. No appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch. CALIFORNIA PROPOSITION 65 WARNING:
Engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects and other reproductive harm. This product may contain or emit chemicals
known to cause cancer, birth defects and other reproductive harm.
Description:
This unit is a combination indoor/outdoor transfer switch and distribution panel.
It can be used as service entrance equipment for 200 Amp services. In addition
to being a transfer switch, this unit provides additional circuits for outdoor
applications such as air conditioner compressors, sewage lift pumps, boat
docks, outbuildings, garages, pump houses, barns and the like. These 200 amp
series models will accommodate 12 single pole circuits.
This transfer switch is made up of five basic elements:
1.
200 amp rated Utility Main Breaker
2.
Generator Main Breaker
3.
A 30 or 50 amp 125/250 volt inlet pre-wired to the generator breaker
4.
A mechanical safety interlock that prevents both Mains from being
"ON" at the same time
5.
A set of sub-feed lugs to handle cable up to 4/0 AWG to feed the
house Main panel.
Tools and Items Needed for Installation:
1/4" and 11/32 nut drivers
Straight blade and Phillips screwdriver
Large Allen wrench Set
Electric drill
Wire cutter/stripper
Anchors and screws to mount switch to wall
Power Cord to connect generator to switch
Compatible Circuit Breaker Types:
Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH,
QAF (Arc Fault), QP (Surge Protector)
Cutler-Hammer Series BD, BR, BQ, GFC
Challenger Type A, C, HAGF
Square D Series HOM (Homeline)
GE Series THQL
CAUTION: If this transfer switch is used as the main service disconnect, it is imperative that all circuit breakers in the transfer switch AND the Main Load Center in the house
be turned OFF when running the system from the generator. Then, turn on only the breakers that the generator can handle at any one time. Check the generator "continuous"
wattage rating to determine the total wattage of connected load. It may be necessary as well as desirable to turn ON and OFF different loads/breakers as needed during an
actual power outage.
Thank you for purchasing a Generac Manual Transfer switch to safely connect a portable
generator to the load center in your home or business (single phase only) for standby power
applications. Product features include:
Generator and Utility Mains mechanically interlocked preventing utility or generator power back feed.
Full branch circuit protection with Siemens
12 gauge High Corrosion-resistant aluminum cabinet.
Ample ground and neutral termination positions for all branch circuits.
Extra spaces for branch circuit breakers.
Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits.
Accepts a Switched Neutral Kit (Model 6297). See Note on Neutral Bonded Generators found above
Table 1.
1
®
circuit breakers.

Advertisement

Table of Contents
loading

Summary of Contents for Generac Power Systems GenTran 6335

  • Page 1 WARNING: Generac transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators. Generac accepts no responsibility for accidents, damages or personal injury caused by incorrect installation. This transfer switch is intended for surface mounting OUTDOORS. Our transfer switches are UL listed to UL Standard 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems.
  • Page 2: Specifications

    If it can be disabled, then no modifications to your transfer switch installation are needed. If the neutral bond cannot be removed or voids the warranty, you must install a Switched Neutral Kit (SNK, Generac model 6297) accessory with your transfer switch.
  • Page 3: Step 2: Using Your Transfer Switch

    Protected by US Patent No. US 6,861,596 B2 Generac Power Systems, Inc. Toll Free: 1-888-GENERAC www.generac.com 0196970SBY PN 50925 Rev A © 2012 Generac Power Systems, Inc. All Rights Reserved. GenTran and Generac are registered trademarks of Generac Power Systems, Inc.
  • Page 4: Instructions D'installation Et D'utilisation

    être installés par un électricien professionnel qui se connaît bien en câbles et codes électriques et a de l'expérience avec les génératrices. Generac décline toute responsabilité pour les accidents, les dommages ou les blessures causés par une installation incorrecte. Ce commutateur de transfert sera monté...
  • Page 5: Étape 1 : Procédure D'installation

    Si la connexion du neutre à la masse ne peut pas être désactivée ou si cela annule la garantie de la génératrice, vous devez installer l'accessoire appelé bloc neutre commuté (SNK, modèle Generac 6297) avec le commutateur de transfert. NOTE : La désactivation de la connexion du neutre à la masse devrait être effectuée seulement par le concessionnaire de la génératrice ou un électricien qualifié.
  • Page 6: Utilisation Du Commutateur De Transfert

    Protégé par le brevet américain no. US 6.861.596 B2 Generac Power Systems, Inc. Numéro gratuit : 1-888-GENERAC www.generac.com © Generac 2012 Power Systems, Inc. Tous droits réservés. GenTran et Generac sont des marques déposées de Generac Power Systems, Inc. 50925 Rév. A...
  • Page 7 Generac no acepta responsabilidad alguna por accidentes, daños o lesiones personales causadas por una instalación incorrecta. Este interruptor de transferencia está...
  • Page 8: Tipos De Disyuntores Compatibles

    Si la unión neutral se quita, el generador ya no pasará la inspección OSHA en lugares de trabajo. TABLA 1: ESPECIFICACIONES MODELO: 6382 6335 Se incluye el interruptor PRINCIPAL DEL SERVICIO ELÉCTRICO. 200 Amp 200 Amp Se incluye el interruptor PRINCIPAL DEL GENERADOR.
  • Page 9 Realice los pasos anteriores al menos UNA VEZ AL MES para mantener el generador adecuadamente "ejercitado". Generac Power Systems, Inc. Línea gratuita: 1-888-GENERAC www.generac.com © 2012 Generac Power Systems, Inc. Todos los derechos reservados. GenTran y Generac son marcas registradas de Generac Power Systems, Inc. 50925 Rev. A...