Fault Shutdowns
The generator set shuts down automatically under the
fault conditions listed in Figure 2-3 and the controller
displays a fault code.
The generator set cannot be
restarted until the fault condition is corrected and the
controller
is reset.
See Section 2.3.5 to reset the
controller after a fault shutdown.
The controller resets
automatically
after a battery voltage fault condition is
corrected.
The
shutdown
switches
on
the
generator
set
automatically reset when the problem is corrected. The
high engine temperature
switch automatically
resets
when the generator set cools. However, the fault does
not clear until the controller is reset.
The controller displays a fault code but the generator set
does not shut down under the conditions
shown in
Figure 2-4.
Code
Fault
AF
Auxiliary fault
input shutdown
Description
Input from a customer-supplied switch that closes when the
fault is active. The generator set shuts down and will not start
when the fault is active (input is grounded),
Check
Check the cause of the auxiliary fault.
HE
High engine
Shutdown occurs if the engine coolant temperature exceeds
Check for blocked air inlets and exhaust
temperature
the maximum temperature for more than 5 seconds,
This
outlets,
shutdown
protective
becomes active after the engine reaches the crank
disconnect
speed,
LOP
Low oil pressure
Shutdown occurs if a low oil pressure condition exists 7
Check for leaks in the lubdcation system,
shutdown
seconds after the engine has reached crank disconnect
speed.
Check the oil level and add oil if the level
Note: The low oil pressure shutdown does not protect against
is low.
low oil level, Check the oil level at the engine,
OC
Overcrank
Shutdown occurs after 3 unsuccessful
starting attempts.
The
Check the fuel supply, spark plug, and
shutdown
crank cycle is set for three starting attempts of 15 seconds
battery.
cranking and 15 seconds rest.
Check for loose connections.
The generator set also shuts down after 1 crank attempt if no
Contact an authorized distributor/dealer
for
speed signal is sensed,
Shuts down 1 second after the fault is
service if problem continues.
detected.
OF
Overfrequency
Shutdown occurs when the governed frequency exceeds 110%
Contact an authorized distributor/dealer
for
shutdown
of the system's frequency setpoint for more than 1 second,
service if problem continues.
This protective becomes active 30 seconds after engine start.
OS
Overspeed
Shutdown occurs if the engine speed exceeds 115% of the
Contact an authorized distributor/dealer
for
shutdown
normal running speed for more than 1 second,
service if problem continues.
OU
Overvoltage
Shutdown occurs if the voltage exceeds 120% of the voltage
Contact an authodzed distributor/dealer
for
shutdown
regulator setpoint for more than 1 second,
service if problem continues.
UF
Underfrequency
Shutdown occurs when the governed frequency falls 1 Hz
Reduce the load and restart the generator
shutdown
below the system's frequency setpoint for more than 1 second,
set,
Contact an authodzed distributor/dealer
for
service if problem continues.
UU
Undervoltage
Shutdown occurs if the voltage falls below 80% of the voltage
Reduce the load and restart the generator
shutdown
regulator setpoint for more than 1 second.
This protective
set,
becomes active 30 seconds after engine start.
Contact an authorized distributor/dealer
for
service if problem continues.
Figure
2-3
ADC
Fault
Shutdown
Codes
Code
Fault
Check
HB
High battery
Check the battery rating and condition.
voltage warning
LB
Low battery
voltage warning
Description
Fault code is displayed
if the engine starting battery voltage rises
above 16 VDC for a 12 VDC system or above 30 VDC for a
24 VDC system for more than 10 seconds when the engine is not
running,
This fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a
voltage within the limits for more than 10 seconds.
Fault code is displayed
if the engine starting battery voltage falls
below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC
system for more than 10 seconds when the engine is not running.
This fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns to a
voltage within the limits for more than 10 seconds.
Check the battery charger operation.
Check the battery rating and condition.
Check the battery charger operation.
Charge or replace the battery.
Figure 2-4
ADC Fault Warning Codes
TP-6195
1/04
Section 2 Operation
5