Greenheck NYD Installation, Operation And Maintenance Manual

Greenheck NYD Installation, Operation And Maintenance Manual

Tamper-resistant centrifugal roof exhaust

Advertisement

Quick Links

®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting
to assemble, install, operate or maintain the product described. Protect yourself and others by
observing all safety information. Failure to comply with instructions could result in personal injury
and/or property damage!
Model NYD
Direct Drive
Model
NYD
is
a
direct
centrifugal roof exhaust fan. These
fans
are
specifically
for
applications
where
resitance is necessary. Performance
capabilities range up to 3,000  cfm
(5,097  m
/hr) and up to 1.0  in.  wg
3
(249 Pa) of static pressure. The maximum continuous
operating temperature for fan sizes 075-140 is 180°F
(82°C). NYD fans are available in six sizes with
nominal wheel diameter ranging from 8 to 14 inches
(203  to 356 mm) (075 - 140 unit sizes). Each fan shall
bear a permanently affixed manufacturer's engraved
metal nameplate containing the model number and
individual serial number.

General Safety Information

Only qualified personnel should install this fan.
Personnel should have a clear understanding of
these instructions and should be aware of general
safety precautions. Improper installation can result
in electric shock, possible injury due to coming in
contact with moving parts, as well as other potential
hazards. Other considerations may be required
if high winds or seismic activity are present. If
more information is needed, contact a licensed
professional engineer before moving forward.
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power source
can result in fire, shock or serious injury.
CAUTION
When servicing the fan, motor may be hot enough to
cause pain or injury. Allow motor to cool before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
Tamper-Resistant Centrifugal Roof Exhaust
drive
designed
tamper
Models NYD & NYB • Tamper-Resistant Centrifugal Roof Exhaust Fans
Model NYD & NYB
Model NYB
Belt Drive
Model NYB is a belt drive centrifugal
roof exhaust fan. These fans are
specifically designed for applications
where tamper resistance is necessary.
Performance capabilities range up to
8,000 cfm (13,592 m
1.0 in. wg (249 Pa) of static pressure.
The maximum continuous operating temperature is
180°F (82°C). NYB fans are available in four sizes with
nominal wheel diameter ranging from 11 to 24 inches
(279 to 610 mm) (100 - 240 unit sizes). Each fan shall
bear a permanently affixed manufacturer's engraved
metal nameplate containing the model number and
individual serial number.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC) and
the National Fire Protection Agency (NFPA),
where applicable. Follow the Canadian Electric
Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be
free to rotate without striking or rubbing any
stationary objects.
3. Motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than max cataloged
fan RPM. Adjustments to fan speed significantly
effects motor load. If the fan RPM is changed,
the motor current should be checked to make
sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces,
or chemicals. Replace cord immediately if
damaged.
6. Verify that the power source is compatible with
the equipment.
7. Never open access doors to a duct while the fan
is running.
PN 463277
/hr) and up to
3
1

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck NYD

  • Page 1: General Safety Information

    PN 463277 Model NYD & NYB ® Tamper-Resistant Centrifugal Roof Exhaust Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information.
  • Page 2 Unpacking storage. The user assumes responsibility of the fan and accessories while in storage. Greenheck Fan Verify that all required parts and the correct Corporation will not be responsible for damage quantity of each item have been received. If any during storage.
  • Page 3: Inspection And Maintenance During Storage

    Pre-Starting Checks The unit should be stored at least 3½ inches (89 mm) off the floor on wooden blocks covered with 1. Check all fasteners and setscrews for tightness. moisture proof paper or polyethylene sheathing. The wheel should rotate freely and be aligned Aisles between parts and along all walls should as shown in figure 2.
  • Page 4 Model NYB 13. The adjustable motor pulley is factory set for the RPM specified. Speed can be increased by Pre-Starting Belt Tension Checks closing or decreased by opening the adjustable 6. Always loosen tension enough to install belts motor pulley. Two groove variable pitch pulleys without stretching, see figure 4.
  • Page 5 5. Shaft bearings can be classified in two groups: IMPORTANT relubricating and non-relubricating. All bearings Adjust (tighten) belt tension after the first are factory lubricated and require no further 24-48 hours of operation. lubrication under normal use (between -20ºF and 180ºF in a relatively clean environment).
  • Page 6: Troubleshooting

    Recommended Relubrication Table 3: Grease Manufacturers Frequency in Months Manufacturer Grease (NLGI #2) U.S. Electric Motors Grease No. 83343 NOTE: If unusual environment conditions exist more Chevron U.S.A. Inc Chevron SRI Grease #2 frequent lubrication is required (extreme temperature, moisture or contaminants). Mobilith Mobil Oil Corporation Mobil 532...
  • Page 7: Parts List

    Parts List NOTE: Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information will assist the local Greenheck representative and the factory in providing service and replacement parts. Before taking any corrective action, make certain unit is not capable of operation during repairs. CAUTION: A fan manufactured with an explosion resistant motor does not certify the entire unit to be explosion proof.