Volt Thermostat Wiring; Volt Humidifier; Gas Supply And Piping - Goodman GKS9 Installation Instructions Manual

Gks9 series gas-fired warm air furnace
Hide thumbs Also See for GKS9:
Table of Contents

Advertisement

*
*
*
STANDARD
*
*
*
JUNCTION BOX
LOCATION
Junction Box Relocation
HIGH VOLTAGE!
T
O AVOID THE RISK OF INJURY
,
DEATH
THE FURNACE MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN
,
THEIR ABSENCE
WITH THE LATEST EDITION OF THE
N
E
C
.
ATIONAL
LECTRIC
ODE
To ensure proper unit grounding, the ground wire should run from
the furnace ground screw located inside the furnace junction box
all the way back to the electrical panel. NOTE: Do not use gas
piping as an electrical ground. To confirm proper unit grounding,
turn off the electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection
and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which
interrupts unit voltage when the blower door is opened for servic-
ing. Do not defeat this switch.
24 V
T
W
OLT
HERMOSTAT
IRING
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.
Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located adja-
cent to the junction box locations in the blower compartment. Wire
routing must not to interfere with circulator blower operation, filter
removal, or routine maintenance. Refer to the following figure for
thermostat connections to the integrated control module terminal
strip.
Y
W
W
R
R
G
C
HEATING
ROOM
FURNACE
THERMOSTAT
Thermostat Diagram
This furnace is equipped with a 40 VA transformer to facilitate use
with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and
24 Volt wiring.
*
ALTERNATE
JUNCTION BOX
*
*
LOCATION
WARNING
,
ELECTRICAL SHOCK OR
Y
W
Y
W
R
R
G
G
C
HEATING AND
FURNACE
COOLING ROOM
CONDENSING
THERMOSTAT
24 V
H
OLT
UMIDIFIER
The yellow wire connected to the I.D. Blower pressure switch is
powered anytime the pressure switch is closed and provides 24
VAC humidifier control. Remove the yellow wire and connect a field
supplied jumper wire with a "piggyback" terminal to the pressure
switch terminal. Reconnect the yellow wire to the "piggyback" ter-
minal on the jumper wire and then connect the 24 VAC line of the
humidifier to the stripped end of the jumper wire. Using a wire nut
or a field-supplied quick connect terminal can make this connec-
tion. The wiring must conform to all local and national codes. Con-
nect the COM side of the humidifier to the B/C terminal on the
furnace control board (or to the COM side of the 24 VAC trans-
former). DO NOT CONNECT 115V HUMIDIFIER TO THESE TERMI-
NALS.
G
ENERAL
The furnace rating plate includes the approved furnace gas input
rating and gas types. The furnace must be equipped to operate on
the type of gas applied. This includes any conversion kits required
for alternate fuels and/or high altitude.
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE
GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE
ADJUSTING THE GAS VALVE PRESSURE REGULATOR
Inlet gas supply pressures must be maintained within the ranges
specified below. The supply pressure must be constant and avail-
able with all other household gas fired appliances operating. The
minimum gas supply pressure must be maintained to prevent
unreliable ignition. The maximum must not be exceeded to pre-
vent unit overfiring.
Natural Gas
Propane Gas
H
A
IGH
LTITUDE
When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied. This is required due to the
natural reduction in the density of both the gas fuel and combus-
tion air as altitude increases. The kit will provide the proper design
certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation alti-
tude and usage of either natural or propane gas. Contact your
Y
distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer's high altitude (Natural, Propane Gas,
C
and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pressure to a
lower pressure than specified on the furnace rating plate. The
combination of the lower air density and a lower manifold pressure
REM OTE
will prohibit the burner orifice from drawing the proper amount of
UNIT
air into the burner. This may cause incomplete combustion, flash-
back, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude. If the gas is artifi-
cially derated, the appropriate orifice size must be determined
based upon the BTU/ft
24
XII. GAS SUPPLY AND PIPING
CAUTION
. O
NLY MINOR ADJUSTMENTS SHOULD BE MADE BY
Inlet Gas Supply Pressure
Minimum: 4.5" W.C. Maximum: 10.0" W.C.
Minimum: 11.0" W.C. Maximum: 13.0" W.C.
D
ERATE
3
content of the derated gas and the altitude.
,
THE
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents