Canadian Applications - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Canadian Applications

Appendix F
This section illustrates the connection of the 411UDAC Digital Alarm Communicator/Transmitter (DACT) to an
FACP for Canadian Applications. The following conditions must be adhered to in order to comply with Canadian
requirements.
Only one FACP can be connected to the 411UDAC DACT.
1.
Phone lines must exit the building in separate directions.
2.
The 411UDAC DACT relay #1 must be enabled [refer to "Output Relay #1 Enable (85)" on page 49] and must
3.
be programmed to activate on DACT trouble [refer to "Output Relay #1 Function Selections (86)" on page
49].
The Auxiliary Trouble Input wiring from the 411UDAC DACT must be in conduit and in the same room as
4.
the FACP and DACT.
82
Canadian Applications
411UDAC
FACP
411UDAC
-24 VDC nonresettable power from FACP
2.2K ELRs P/N 27070
Document #51073
Rev. D 12/09/2008
Relay Output (DACT
Trouble) from 411UDAC
Auxiliary Trouble Input
(nonsupervised, power-limited)
P/N 51073:D