Optional Programmer

2.7
Optional Programmer
The Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to:
switch between the digital alarm communicator's five Modes of operation
set the digital alarm communicator's 24 hour internal clock in Real-Time Clock Mode
program the 411UDAC digital alarm communicator in Program Mode
test the status of input and output circuits (including telephone lines) in Troubleshoot Mode
return all digital alarm communicator programming to the factory default settings in Default Mode
To use the PRO-411 Programmer:
Remove all power from the 411UDAC
1.
Unlock and open the 411UDAC door
2.
Connect the Programmer cable to connector J2 located in the lower right corner of the 411UDAC. Note that
3.
the key on the connector must align with the slot in the J2 connector
Reapply power to the 411UDAC
4.
Operate the Programmer by pressing the MODE key. Enter the appropriate four digit code and then press the
5.
[ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the four Channels is programmed
for fire alarm or fire supervisory and is active, that is, in alarm (shorted).

Programmer Connection to 411UDAC

FIGURE 2-11:
411UDAC
NOTE: The Fire•Watch 411 Series DACT Programmer
must be removed when not in use.
- +
411UDAC
Document #51073
Programmer
J2 connector
Rev. D 12/09/2008
P/N 51073:D
Cable attached
to Programmer
29