Telephone Requirements And Warnings; Telephone Circuitry - Ph1 & Ph2; Digital Alarm Communicator; Telephone Company Rights And Warnings - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Telephone Requirements and Warnings

1.9
Telephone Requirements and Warnings
1.9.1 Telephone Circuitry - PH1 & PH2
AC Ringer Equivalence Number (REN) = 1.2B
DC Ringer Equivalence Number (REN) = 0.0B
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con-
nected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.

1.9.2 Digital Alarm Communicator:

Before connecting the 411UDAC to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer:
Product Model Number: 411UDAC
FCC Registration Number: OAAUSA-25431-AL-E
AC Ringer Equivalence: 1.2B
DC Ringer Equivalence: 0.0B
Note: FCC ID label is located on the inside cover.
Important! The DACT must not be used to dial a phone number that is call-forwarded per requirements of UL 864
9th Edition.

1.9.3 Telephone Company Rights and Warnings:

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this digital communicator. How-
ever, the telephone company is required to give advance notice of such changes or interruptions. If the digital com-
municator causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private tele-
phone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
16
Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472
411UDAC
Document #51073
Rev. D 12/09/2008
P/N 51073:D