Explanation of console messages
Response
Notify maintenance staff.
SXSM054
sma#: CPU <Id> automatically throttled
ALERT
Meaning
The CPU performance has been reduced because the CPU temperature was high. This is
designed to prevent the CPU from becoming any hotter and entering the critical tempera-
ture range.
The increase in the CPU temperature can, for example, be caused by a fan which is no lon-
ger fully operational (e.g. if a fan prefailure has occurred).
Response
Notify maintenance staff.
SXSM055
sma#: Fan <Id> is not installed
ALERT
Meaning
Fan <Id> is not installed or has failed. If the fan concerned is inoperable for more than 3
minutes, the SINIX system is shut down and the server is switched off to prevent the server
from becoming too hot.
Response
Notify maintenance staff.
SXSM056
sma#: Memory automatically throttled; Module# = <Id>
ALERT
Meaning
The memory performance performance has been reduced because the temperature in me-
mory module <Id> was high. This is designed to prevent the memory module from beco-
ming any hotter and entering the critical temperature range.
The increase in the memory temperature can, for example, be caused by a fan which is no
longer fully operational (e.g. if a fan prefailure has occurred).
Response
Check the ambient temperature and the fan situation Notify maintenance staff if required.
SXSM057
sma#: Memory device critical overtemperature; Module# = <Id>
ALERT
Meaning
Excessive temperatures were detected in memory module <Id>.
The increase in the memory temperature can, for example, be caused by a fan which is no
longer fully operational (e.g. if a fan prefailure has occurred).
U41117-J-Z125-7-76
Message lines
507