ALARM CODE DESCRIPTIONS
Code
Alarm name
49
Low suction overheat, circuit B
50
Low oil pressure, compressor A1
51
Low oil pressure, compressor B1
52
Low oil pressure, compressor A2
53
Low oil pressure, compressor B2
54
Low oil pressure, compressor A3
55
Low oil pressure, compressor B3
56
Low oil pressure, compressor A4
57
Low oil pressure, compressor B4
58
Evaporator water flow control fault
59
Low pressure fault, circuit A
60
Low pressure fault, circuit B
61
Repeated high pressure load sheds, circuit A
62
Repeated high pressure load sheds, circuit B
63
High pressure switch not reset or reverse compressor
rotation, circuit A
64
High pressure switch not reset or reverse compressor
rotation, circuit B
65
Control box thermostat fault
66
Loss of communication with System Manager
67
Loss of communication with the master or slave
68
Master/slave configuration error
69
Initial factory configuration necessary
70
Poor factory configuration.
1. Compr. A3 configured and A2 absent
2. Compr. A4 configured and A2 or A3 absent
3. No lead compr. in circuit B
4. Compr. B3 configured and B2 absent
5. Compr. B4 configured and B2 or B3 absent
6. Difference of compressors in circ. A and B too high
7. Fan configured for a water-cooled condenser
8. No fans configured
9. Heat reclaim option configured, and heat reclaim
sensors not configured
71
CCN/Clock Board fault
72
Emergency stop
73
Pump No. 1 fault
74
Pump No. 2 fault
75
Condenser anti-freeze protection, circuit A
76
Condenser anti-freeze protection, circuit B
77
Lack of water flow, condenser
78
Condenser water flow fault, heat reclaim mode
79
Heat reclaim mode fault, circuit A
80
Heat reclaim mode fault, circuit B
81
High pressure fault, circuit A
82
High pressure fault, circuit B
83
Maintenance alert
1. Charge too low
2. Water loop too low
3. Air filter maintenance delay elapsed
4. Pump 1 maintenance delay elapsed
5. Pump 2 maintenance delay elapsed
6. Water filter maintenance delay elapsed
34
Description
Action
Circuit B shut down
Oil pressure < min. threshold
Circuit A shut down
Ditto
Circuit B shut down
Ditto
Compressor A2 shut down
Ditto
Compressor B2 shut down
Ditto
Compressor A3 shut down
Ditto
Compressor B3 shut down
Ditto
Compressor A4 shut down
Ditto
Compressor B4 shut down
1. Interlock not closed before end
Unit shut down.
of start-up delay
Pump shut down
2. Pump shut down for 2 mins
and water flow contact closed
Circuit operating, and suction pressure
Circuit A shut down
below permitted threshold for more
than 3 mins.
Ditto
Circuit B shut down
More than 6 successive capacity load
None
sheds in the circuit due to exceeded
high pressure
Ditto
Ditto
The high pressure switch has not been
Circuit A shut down
reset after a high pressure cut-out,
or the lead compressor does not work
Ditto
Circuit B shut down
Sensor overheat
Unit shut down
Units controlled by SM, and
Unit operates in autonomous mode
communication with the module over
2 mins. faulty
Master/slave connection interrupted
Unit operates in autonomous mode
beween the two units for more than
2 mins.
Poor master/slave configuration
Master/slave control not allowed
All factory parameters are at zero
Unit prevented from starting
Poor factory configuration
Ditto
The CCN/Clock Board is no longer
Unit shut down
detected
An emergncy stop commend has been
Unit shut down
transmitted by the CCN network.
Evaporator water pump operating
Unit shut down
contact open, when the pump has
received a commmand to operate.
Ditto
Unit shut down
Saturated temperature is under the
Unit shut down. Condenser pump
frost cut-out point
started, if unit is shut down
Ditto
Ditto
Water flow switch (water-cooled units) Unit shut down
not closed for 1 min.
Ditto
Units stays in cooling mode
More than two consecutive pumpdown Circuit A stays in cooling mode
sequences not successful
Ditto
Circuit B stays in coolng mode
Circuit operating and discharge pressure Unit shut down
exceeds the high pressure cut-out point
Ditto
Ditto
A maintenance alert is active
None
Pumpdown
Reset type
Probable cause
Yes
Manual
Ditto
No
Manual
Compressor, crankcase
heater, pressure sensor or
EXV faulty, refrigerant
charge too high, low oil
charge
No
Manual
Ditto
Manual
Ditto
Manual
Ditto
Manual
Ditto
Manual
Ditto
Manual
Ditto
Manual
Ditto
No
Manual
Evaporator water flow fault
No
Auto first time,
Low refrigerant charge, EXV
then manual*
faulty or filter dirty
No
Ditto
Ditto
No
Auto
Transducer faulty, condenser
ent. air temp., evaporator ent.
water temp. too high, cond.
blocked or fan flow rate too
low
Ditto
Ditto
No
Manual
The high pressure switch has
not been reset, poor electrical
connection of lead compr.
No
Manual
Ditto
Manual
Control box poorly
ventilated
Auto
CCN network fault
Auto
CCN network fault
Auto/manual in
Master/slave configuration
case of heating/
fault
cooling fault
Auto
No factory configuration
Ditto
Factory configuration error
No
Auto, if the board CCN/Clock Board faulty
is again detected
No
CCN
CCN network command
No
Manual
Pump overheat or poor
pump connection
No
Manual
Ditto
No
Auto
Discharge pressure trans-
ducer faulty, refrigerant leak,
or low cond. water temp.
No
Auto
Ditto
No
Manual
Condenser pump, low water
flow, water flow switch
No
Manual
Ditto
No
Manual
Leak or heat reclaim or drain
solenoid shut-off valve fault
No
Manual
Ditto
No
Manual, the high
Fan circuit fault, air or
pressure command condenser temperature too
must be reset
high
manually by the
button on the HP
pressure switch
No
Ditto
Ditto
Manual