Bryant PREFERRED T6-PRH-A Installation Instructions & Replacement Parts List

Bryant PREFERRED T6-PRH-A Installation Instructions & Replacement Parts List

Preferred series thermidistat programmable / non-programmable control
Hide thumbs Also See for PREFERRED T6-PRH-A:
Table of Contents

Advertisement

T6- -PRH- -A, T6- - NRH- - A
PREFERREDt SERIES
THERMIDISTAT
Installation Instructions
A07045
Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
A07044
Non ---Programmable Control

Advertisement

Table of Contents
loading

Summary of Contents for Bryant PREFERRED T6-PRH-A

  • Page 1: Installation Instructions

    T6- -PRH- -A, T6- - NRH- - A PREFERREDt SERIES THERMIDISTAT Installation Instructions A07045 A07044 Programmable Control Non ---Programmable Control NOTE: Read the entire instruction manual before starting the installation.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS ........INTRODUCTION .
  • Page 3: Introduction

    -configured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Bryant’s proven line of thermostats; it provides separate setpoints for heating and cooling in addition to humidification and dehumidification.
  • Page 4: Installation Considerations

    INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low- -voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper.
  • Page 5 There are programmable and non- -programmable models for all applications. They can be configured for AC or HP, 1- -or 2- -speed compressor, and for Hybrid Heatt installations, allowing it to be used in place of all Bryant thermostats. Programmable Thermidistat Controls may be configured as non- -programmable if user desires.
  • Page 6 WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. DO NOT connect furnace HUM terminal directly to Thermidistat Control HUM terminal. This will bypass furnace safety controls. See Low Voltage Wiring Diagrams and notes for proper connection.
  • Page 7 Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable model, where it is desirable to install the Thermidistat Control in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor.
  • Page 8: Installation

    INSTALLATION Carton contains the following components. See Fig. 2 for T6- -PRH or Fig. 3 for T6- -NRH. A07752 Fig. 2 - - T6- -PRH- -A Carton Contents 1. Display Module 2. Stand- -off for Equipment Control Module 3. Outside Air Temperature Sensor, screws and pigtail. 4.
  • Page 9 A07753 Fig. 3 - - T6- -NRH- -A Carton Contents 1. Display Module 2. Stand- -off for Equipment Control Module 3. Outside Air Temperature Sensor, screws and pigtail. 4. Equipment Control Module Thermidistat Control Location Thermidistat Control should be mounted: Approximately 5 ft (1.5m) from floor.
  • Page 10 Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature- -radiating objects which could cause a false reading. Close to or in direct airflow from supply registers and return- -air regis- ters. In areas with poor air circulation, such as behind a door or in an al- cove.
  • Page 11 CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage Thermidistat Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1.
  • Page 12 CAUTION ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage. Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly. Two- - Piece Installation The following steps should be followed for the installation of the two- -piece configuration.
  • Page 13 A07225 Fig. 4 - - Press Tabs to Remove Backplate A07226 Fig. 5 - - Take Apart...
  • Page 14 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev- eled for proper operation) and mark wall through 2 mounting holes. See Fig. 6. A07165 Fig. 6 - - Backplate Mounting 3.
  • Page 15 6. Match and connect equipment wires to proper terminals of each connector block, being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base. If wires are con- nected incorrectly, the Display Module will not operate.
  • Page 16 A07166 Fig. 8 - - Secure Wires to Terminal Strip A07167 Fig. 9 - - Connect Pigtail Wires to Display Module...
  • Page 17 NOTE: The 2- -wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the Equipment Control Module screw terminals. S Red of the pigtail is V+ S Black of the pigtail is Vg 7.
  • Page 18 10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.). A07217 Fig.
  • Page 19 A07227 Fig. 12 - - Standoff NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base.
  • Page 20 A07218 Fig. 13 - - Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- -digit code appears on large display which identifies Thermidistat Control configuration.
  • Page 21 Single- - Piece Installation The following steps should be followed for the installation of the single- -piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module.
  • Page 22 A07219 Fig. 14 - - Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature and/or humidity measurement.
  • Page 23 A07221 Fig. 15 - - Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2- -digit code appears on large display which identifies Thermidistat Control configuration. Refer to Option 33. a.
  • Page 24 Set Thermidistat Control Configuration Configuration options enable the installer to configure the Thermidistat Control for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual.
  • Page 25 Option 11 — Adjustable Setpoint Deadband (not available on heat only and cool only systems) Option 12 — Smart Recovery (programmable models only) Option 13 — Room Temperature Offset Adjustment Option 14 — Humidity Offset Adjustment Option 15 — Enable Auto Mode Option 16 —...
  • Page 26 Option 31* — Daylight Savings Time Configuration (programmable models only) Option 32 — Furnace Heat Staging Option 33 — Single or Two- -Piece Installation Option 40 — Fan Humidify Option 41 — Variable Speed Blower Option 42 — Variable Speed Super Dehumidification Option 43 —...
  • Page 27 saved at the time of selection and will be saved in the event of the 3 minute time- -out or when installer exits from configuration menu. Configuration Options —Selection Option 01 — Equipment Type Range: H2, A2, HP, AC, hh, h2, H, C H2 —...
  • Page 28 Option 03 — Fahrenheit/Centigrade Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is Fahrenheit (F). Option 04 — Fan (G) On With W/W1 This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On.
  • Page 29 time guard and cycle timers. The minimum On time is still controlled by the Thermidistat Control. Default is OF (off). Option 08 — Auxiliary Heat Lockout Temperature This selection is available on heat pump systems with a valid outdoor temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
  • Page 30 on heat pump operation. “O” is used to describe a heat pump system that energizes its reversing valve in cooling. “B” is used to describe a heat pump system that energized its reversing valve in heating. H — Reversing valve output (O/W2/B) is energized when HEAT mode is selected.
  • Page 31 Option 14 — Humidity Display Offset Adjust The percentage to be added to the displayed humidity to calibrate or deliberately miscalibrate the measured room humidity (- -9% to +9% RH). Default is 0. Option 15 — Enable Auto Mode This selection is not available if the Thermidistat Control is configured as Heat Only or Cool Only in Option 1.
  • Page 32 Option 17 — Time Between Equipment Stages This selection is only available for heat pump systems. This determines the minimum number of minutes of equipment operation on the highest compressor stage before allowing the transition to auxiliary heat. Available selections are 10, 15, 20, and 25.
  • Page 33 the period or minutes and then use the UP/DOWN buttons to change to the desired value. 2 — The dry contact will operate as a DH relay. This relay is reverse logic. When the humidity level is above the dehumidify setpoint, the dry contact D1- -D2 will be opened.
  • Page 34 Option 20 — Outdoor Air Temperature Offset Adjustment This selection allows the calibration, or deliberate miscalibration of the outdoor air temperature sensor reading. The selection ranges from - -5 to +5_. Default is 0. Option 21 — Keypad Lockout (programmable models only) This selection allows the installer to limit access to the keypad.
  • Page 35 1 — The user has access to modify Home, Sleep, Away, and UP/DOWN setpoints. 2 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed. When the keypad lock selection is turned on, the padlock icon will be displayed.
  • Page 36 On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all cooling demands. Default is OF (off). Option 23 — High Heat Latch Temperature (only available if outdoor sensor is present) This selection is only available when Option 1 is set to H2, or h2 and Option 7 (zoning) is set to OF (off).
  • Page 37 four periods is more common for residential. This selection is not available if Option 24 has been set to nP to configure the Thermidistat Control for non- -programmable operation. 2 — Periods DAY and SLEEP are available 4 — Periods WAKE, DAY, EVE, and SLEEP are available. Default is 4.
  • Page 38 6- -48 — The number of months after which the UV Light reminder will be displayed, “CHECK UV LIGHT”. Default is OF (off). Option 29 — Humidifier Pad Reminder This selects the number of months after which the Humidifier Pad Reminder icon will be displayed.
  • Page 39 Option 31 — Daylight Savings Time Configuration (programmable models only) This selection allows the installer to set the Thermidistat Control to automatically change by one hour on the specified day, month, and week specified. OF (off) — Daylight Savings Time Function disabled. 1,2 On —...
  • Page 40 Option 33 — Single or Two- -Piece Installation This configuration allows the Thermidistat Control to compensate for the amount of heat generated by the Thermidistat Control electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two- -piece installation.
  • Page 41 On - - The system has a variable speed blower. Factory default is OF (Off) Option 42 — Variable Speed Super Dehumidification This option will only be available if the Variable Speed Blower setup (Option 41) has been set to ON. OF - - The fan output (G) is energized when the compressor is on for cool to dehumidify functionality.
  • Page 42 Option 44 — Super Comfort Heat This option is only available on heat pump units HP (HP, H2, hh, and h2) when Option 41 (Variable Speed Blower) is set to On and the system has a valid OAT sensor. OF (Off) - - Comfort Heat is off On - - Comfort Heat feature is on.
  • Page 43: System Start- -Up And Checkout

    Option 99 — Reset to Factory Defaults Use this capability to reset the Thermidistat Control to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and calendar which have been manually entered will be lost! When this option is selected, the configuration number (99), will appear on the left and 10 will appear on the right.
  • Page 44 Heat - - The first stage of heating will be energized for three minutes, then the first and second stages (if a second stage exists) will turn on for an additional three minutes. During the first stage of heating, the HEAT ON icons will be displayed. During the second stage of heating (if one exists), the “2”...
  • Page 45 pressed for fan to turn On and off. On some fan coils, fan continues to operate for 90 sec after G signal is removed. Final Settings Be sure to press DONE to exit installer setup mode. If the system is to be left in operation after installation is complete, use MODE button to select between HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or auto.
  • Page 46 The FAN button may be used to select between AUTO (fan on only with equipment) and On (fan on continuously) fan modes. For further information on temperature selection and programming, refer to Homeowner’s Guide. Setting The Clock, Calendar, Daily Schedule, and Vacation Settings (programmable models only) To set the clock, press the SET button once.
  • Page 47 Humidity Control Features The various humidity control features of the Thermidistat Control are explained below. They are grouped into 2 sections, humidification and dehumidification. Instructions on how to select each feature are given at the end of each section. Humidification The Thermidistat Control directly connects to a standard 24VAC humidifier to control humidification in the home.
  • Page 48 See Fig. 16 for outdoor temperature/indoor humidity relationship in auto humidify mode. 3. Humidify Off The humidify function can be turned off completely. This does not re- quire changing existing setpoints. To Select Humidification (programmable) Press the soft key below the humidify icon to bring up humidity select screen. Humidify options are only available when in Heating mode.
  • Page 49 than setpoint, a dehumidification demand exists. The Thermidistat Control responds by activating the dry contact (when enabled in Option 19). It may also control the compressor and blower, depending on equipment type and dehumidify selection choice. The 3 available selections are described below. A mandatory 5 minute blower off delay will be enforced if there has been a call for dehumidification during a cooling call.
  • Page 50 A06599 Fig. 16 - - Auto Humidity 3. Dehumidify Off Dehumidification can be turned off completely. This can be done without changing existing setpoints. To Select Dehumidification (programmable - - between NORMAL, COOL TO, and OFF) Press the soft key below the dehumidify icon button to bring up dehumidify selections.
  • Page 51 system is in AUTO mode, dehumidify options are available if the last system operation was a call for cooling. To Select Dehumidification (non- -programmable - - between NORMAL, COOL TO, and OFF) Press the features button three times. The first press displays the outdoor air temperature, the second press displays the humidify options and the third press will display the current dehumidify selections.
  • Page 52 Bryant FK and FV series variable- -speed fan coils, all variable- -speed furnaces, and select single and multi- -stage furnaces with the dehumidify connection have dehumidify inputs which connect directly to Thermidistat Control dry contact. Refer to the furnace literature for dehumidification options.
  • Page 53 Vacation Setpoints A special set of temperature and humidity setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 3 for default values. Table 3 –...
  • Page 54: Operational Information

    OPERATIONAL INFORMATION Timers Five- -Minute Compressor Timeguard This timer prevents compressor from starting unless it has been off for at least 5 minutes. It can be overridden for 1 cycle by simultaneously pressing FAN and UP buttons. Cycle Timer Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes.
  • Page 55 signal shall be considered valid if the compressor output is energized and the defrost signal has been active for less than 15 consecutive minutes. Any defrost signal present for longer than 15 minutes shall be considered invalid. Heat pump/fan coil and hybrid heat systems shall use this input to: Detect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle Allow a defrost cycle to run to completion regardless of the system...
  • Page 56 Humidify and Dehumidify Indicators When the Display Module door is closed, the humidify icon will be displayed when humidification is active and the dehumidify icon will be displayed when dehumidification is active. Auto Changeover When auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 20 minutes.
  • Page 57: Troubleshooting

    power to energize the dehumidify terminal on the cooling equipment when the dry contact is closed. If it is desired to operate a ventilator or other device, the D1 and D2 terminals can be connected directly to the equipment. This will provide a closed contact for the specified number of minutes per hour.
  • Page 58 seconds. The control will operate from the temperature sensed by the working sensor. E1 - - If the Display Module and the Equipment Control Module cannot communicate via two- -wire connection, an E1 will be displayed. E2 - - There is no E2 error message. E3 - - If Thermidistat Control cannot properly read outdoor temperature, and it is needed for proper operation, display will indicate “- -- -”...
  • Page 59 Table 4 – Equipment Configuration Outputs EQUIP FACTORY COOL COOL HEAT HEAT HEAT HEAT CONFIG HEAT HEAT CONFIG STG 1 STG 2 STG 1 STG 2 STG 3 STG 4 OPTION 01 STG 1 STG 2 SS AC Y/Y2 W/W1 W/W1 O/W2/B SS AC...
  • Page 60 Table 4 - - Equipment Configuration Outputs (cont) EQUIP FACTORY COOL COOL HEAT HEAT HEAT HEAT CONFIG HEAT HEAT CONFIG STG 1 STG 2 STG 1 STG 2 STG 3 STG 4 OPTION 01 STG 1 STG 2 Y1/W2 Y1/W2 2SPD HP Y1/W2 Y1/W2...
  • Page 61 WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module Fan Coil Heat Pump RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Y/Y2 Y1 / W2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Outdoor Air Temp Remote Room Sensor...
  • Page 62 Equipment Control Module Fan Coil Heat Pump RVS Cooling O/B W2 Remove J2 Heat Stage 3 W/W1 jumper for heat staging Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 jumper for Dry Contact 1 Dehumidify...
  • Page 63 Typical Single-Stage Equipment Control Module Fan Coil Heat Pump RVS Cooling O/B W2 Heat Stage 2 W/W1 Heat Stage 3 Y1 / W2 Heat/Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp...
  • Page 64 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 Aux. Connection 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor *...
  • Page 65 Equipment Control Module Fan Coil Air Conditioner Remove J2 Heat Stage 2 O/B W2 Jumper for heat staging Heat Stage 1 W/W1 Cool Stage 1 Y1 / W2 Cool Stage 2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 jumper for Dry Contact 1 Dehumidify...
  • Page 66 Typical Single-Stage Equipment Control Module Fan Coil Air Conditioner Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve *...
  • Page 67 Equipment Control Module Fan Coil RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 Aux. Connection 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor...
  • Page 68 Equipment Control Module Fan Coil Heat Pump RVS Cooling O/B W2 Remove J2 Heat Stage 2 W/W1 Jumper for Heat Stage 3 Y1 / W2 heat staging Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Remove J1 Jumper for Dry Contact 1 Dehumidify...
  • Page 69 Typical Equipment Control Module Fan Coil RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor...
  • Page 70 Equipment Control Module RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Outdoor Air Temp Remote Room Sensor OAT/RRS Com SRTN A08131...
  • Page 71 Equipment Control Module Fan Coil Air Conditioner Remove J2 Heat Stage 2 O/B W2 Jumper for heat staging Heat Stage 1 W/W1 Y1 / W2 Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating Remove J1 24VAC Hot Cooling Jumper for Dehumidify Dry Contact 1 modes...
  • Page 72 Typical Single-Stage Equipment Control Module Fan Coil Air Conditioner RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 / W2 Compressor High Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp...
  • Page 73 Variable Speed/Multi-Stage Equipment Control Module Furnace Heat Pump RVS Cooling O/B W2 Heat Stage 3 W/W1 W/W1 (furnace) Heat/Cool Stage 1 Y1 / W2 Heat/Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 DHUM Dry Contact 2 24VAC Common Humidify...
  • Page 74 Single-Stage Single-Stage Equipment Control Module Furnace Heat Pump RVS Cooling O/B W2 Heat Stage 2 W/W1 (furnace) Y1 / W2 Heat/Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve *...
  • Page 75 Variable Speed/Multi-Stage Equipment Control Module Furnace Air Conditioner Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Cool Stage 1 Y1 / W2 Cool Stage 2 Y/Y2 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify...
  • Page 76 Single-Stage Single-Stage Equipment Control Module Furnace Air Conditioner O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor *...
  • Page 77 Variable Speed/Multi-Stage Equipment Control Module Furnace Heat Pump RVS Cooling O/B W2 Heat Stage 3 Y1 / W2 (furnace) Heat Stage 2 W/W1 (furnace) Heat/Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify...
  • Page 78 Single-Stage Equipment Control Module Furnace O/B W2 Heat Stage 1 W/W1 Y1 / W2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 DHUM Dry Contact 2 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve * Remote Room Sensor Outdoor Sensor * OAT/RRS Com SRTN...
  • Page 79 Variable Speed/Multi-Stage Equipment Control Module Furnace Air Conditioner Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp...
  • Page 80 Single-Stage Equipment Control Module Furnace Air Conditioner Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Y1 / W2 Cool Stage 1 Y/Y2 Y/Y2 24VAC Hot Heating 24VAC Hot Cooling Dry Contact 1 Dry Contact 2 DHUM 24VAC Common Humidify Humidifier Solenoid Outdoor Air Temp Valve *...
  • Page 81 THERMIDISTAT CONTROL CONFIGURATION RECORD Installer Model Number Date _________________________ ______________________________ _________________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C.
  • Page 82 E Configuration Options Option 01 Equipment Type _____ Option 02 Clean Filter Timer Adjustment _____ Option 03* Fahrenheit/Centigrade Selection _____ Option 04 Fan (G) on with W/W1 Selection _____ Option 05 Room Air Temperature Sensing (programmable models only) _____ Option 06 Cooling Lockout Below 55_F/13_C Selection (only available if outdoor air sensor is present) _____ Option 07...
  • Page 83 E Configuration Options (cont) Option 19 Dry Contact (programmable models only) _____ Option 20 Outdoor Air Temperature Offset Adjustment _____ Option 21* Keypad Lockout _____ Option 22 High Cool Latch Temperature _____ Option 23 High Heat Latch Temperature _____ Option 24* Programmable/Non- - Programmable (programmable models only) _____ Option 25*...
  • Page 84 Reset to Factory Defaults _____ * Options with an asterisk can also be set/changed by the homeowner. E2008 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 03/08 Catalog No: IIT6---PRH ---03 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

This manual is also suitable for:

Preferred t6-nrh-aA07045A07044

Table of Contents