Honeywell Tradeline T8611M Installation Instructions Manual

Deluxe programmable heat pump thermostat
Hide thumbs Also See for Tradeline T8611M:

Advertisement

Quick Links

APPLICATION
The T8611M Deluxe Programmable Heat Pump Thermostat provides electronic control of 24 Vac single-zone two
compressor or two speed heat pump systems with auxiliary heat. The T8611M can be configured to run a single
compressor heat pump system. Refer to Table 1 for a general description of the thermostat. All T8611 thermostats
require a common wire to supply power.
T8611
Changeover
M
Automatic
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority
for instructions regarding recycling and the proper
disposal of the old thermostat.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
®U.S. Registered Trademark
Copyright © 2000 Honeywell •
Table 1. Description of T8611 Thermostats.
System Selection
Em Heat-Heat-
Off-Cool-Auto
• All Rights Reserved
Deluxe Programmable
Heat Pump Thermostat
Fan Selection
On-Auto
Down-selectable for single compressor systems.

Wallplate Installation

Mount the thermostat horizontally on the wall or on a
2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat functions properly even when
not level.
2. Use a pencil to mark the mounting holes. See
Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two 7/32
inch holes. Gently tap anchors (provided) into the
drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling the
wires through the wiring opening.
5. Loosely inser t the mounting screws into the holes.
6. Tighten the mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 and 4 for typical hookup. A
letter code is located near each terminal for identification.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 5.
X-XX UL
INSTALLATION INSTRUCTIONS
Comments
T8611M
69-1415

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Tradeline T8611M

  • Page 1: Wallplate Installation

    See Fig. 5. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall behind the thermostat. ®U.S. Registered Trademark 69-1415 Copyright © 2000 Honeywell • • All Rights Reserved X-XX UL...
  • Page 2 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT 5 FEET [1.5 METERS] M10106 Fig. 1. Typical location of thermostat. THERMOSTAT WALL WIRES THROUGH WALL OUTDOOR TEMPERATURE SENSOR EQUIPMENT EM. HEAT RELAY MONITOR 2 WALL ANCHORS AUX. HEAT RELAY COMPRESSOR CONTACTOR 1 EQUIPMENT MONITOR OR DEFROST RELAY RESET...
  • Page 3: Using Thermostat Keys

    DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT THERMOSTAT OUTDOOR TEMPERATURE SENSOR EM. HEAT EQUIPMENT RELAY ENGAGE TABS AT TOP OF MONITOR 2 THERMOSTAT AND WALLPLATE. COMPRESSOR CONTACTOR EQUIPMENT MONITOR OR DEFROST RELAY RESET CONTROL COOL/HEAT CHANGEOVER VALVE PRESS LOWER EDGE OF CASE AUX.
  • Page 4: Led Indication

    DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT SET WAKE TIMES INCREASE TEMPERATURE AND SETPOINTS SETTING OR SCROLL SET LEAVE TIMES FORWARD THROUGH AND SETPOINTS INCREASE TIME SETTING INSTALLER SETUP OPTIONS OR SCROLL FORWARD THROUGH INSTALLER SETUP SET RETURN TIMES AND SYSTEM TEST AND SETPOINTS DECREASE TEMPERATURE SETTING OR SCROLL...
  • Page 5: Installer Setup

    DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT INSTALLER SETUP System Wait Set Program Set Day/Time Temporary Setting Em Heat Recovery Hold for Cool NOTE: For most applications, the thermostat factory Auto settings do not need changing. Review the Filter Em Ht Aux Ht Days Factory Setting column in Table 3 and if no Repl Batt...
  • Page 6 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT Table 3. Thermostat Installer Setup Options (Continued). Installer Setup Number Other Choices (Press Time Factory Setting (Press key to change) key to Actual change) Setting Select Display Description Display Description Not used. — — — —...
  • Page 7: Installer System-Test

    DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT IMPORTANT INSTALLER SYSTEM-TEST Review the settings to confirm they match the system. Press Run Program to exit the Installer Use the Installer System-Test to check the thermostat Setup. The thermostat has saved the Installer operation. Refer to Table 4 for a list of the system tests. Setup changes and initiated a reset in order to operate using the new settings.
  • Page 8 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT Refer to Table 5 for descriptions of specific system tests. NOTE: Press Time to advance to the next test and press Time to go back to the previous test. Press Run Program to exit the system test. Table 5.
  • Page 9: Thermostat Information

    DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT 4. Press the increase key again to display the THERMOSTAT INFORMATION software revision number (Example: 001=Revision number 1). 1. Press the Time key to access the thermostat information. M14616 5. Press the increase key again to display the M14613 EEPROM identification code (Example: 314 = 2.
  • Page 10 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT Troubleshooting (Continued). Symptom Possible Cause Action Heating will not No power to the thermostat. • Check for 24 Vac between R and C terminals. come on. — If missing 24 Vac: — Check if the circuit breaker is tripped—reset the circuit breaker.
  • Page 11 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT 69-1415...
  • Page 12 DELUXE PROGRAMMABLE HEAT PUMP THERMOSTAT Home and Building Control Home and Building Control Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 429 www.honeywell.com 69-1415 G.H. 8-00 Printed in Taiwan R.O.C.