Electronic Programmable and Non-Programmable Fan Coil Thermostats
6000 series with independent fan common
Specifi cation
Power supply:
24 volt powered models - 20-30 Vac, 50/60Hz
230 volt powered models - 210-250 Vac, 50/60Hz
Temperature range:
Heating stage - Off -5-30°C
Cooling stage - 16-37°C-Off
Temperature accuracy:
± 0.5°C
Deadzone adjustment:
1, 2, 3 or 4°C
Voltage rating of contacts:
20-250 Vac, 50/60Hz
Current rating of contacts:
10mA - 3A resistive, 1A inductive
Switching action:
Voltage free SPDT contacts, Type 1B
Time accuracy:
± 1 minute
Memory retention:
24V & 230V models: 15 days
Battery model: 1 minute for battery change
IP rating:
IP30
Dimensions (mm):
130 x 100 x 38 (W x H x D)
Control pollution situation:
Degree 2
Rated impulse voltage:
2.5 KV
Ball pressure test:
75°C
Applications
HCS & HCST Models
Wiring
HCS & HCST Models with 3 speed fan
(Heat or Cool)
Ordering Details
Features
24 volt
Type
Heat or cool operation, selectable at time of installation
3-speed fan output
HCS6101-3
Heat & cool systems (with auto changeover), for use in 4-pipe systems
3-speed fan output
HC & HCT Models
HC & HCT Models with 3 speed fan
(4 pipe auto change-over)
230 volt
Code
Type
Code
087N722500
HCT6113-3
087N759326
1

Advertisement

loading

Summary of Contents for Danfoss HCS6101-3

  • Page 1 Installation and Setting Instructions Electronic Programmable and Non-Programmable Fan Coil Thermostats 6000 series with independent fan common Ordering Details Specifi cation Features 24 volt 230 volt Power supply: 24 volt powered models - 20-30 Vac, 50/60Hz 230 volt powered models - 210-250 Vac, 50/60Hz Type Code Type...
  • Page 2 Installation 1. Thermostat Location 2. Unpacking the Thermostat 3. Separating the Wallplate 4. Fitting the Thermostat to the Wall 5. Wiring Access - Incorrect 6. Wiring Access - Correct 7. Cable Size Max cable size 1.5mm...
  • Page 3 DIL Switch Settings (see rear of circuit board) HCS Models HC Models CHRONO- CHRONO- ON/OFF ON/OFF PROPORTIONAL PROPORTIONAL COMPRESSOR COMPRESSOR DELAY COMPRESSOR COMPRESSOR DELAY DELAY ON DELAY ON HEATING COOLING NOT USED THERMOSTAT THERMOSTAT NOT USED 4 EVENTS 2 EVENTS EACH DAY 2 EVENTS EACH DAY 4 EVENTS EACH DAY *...
  • Page 4 Danfoss can accept no responsibilty for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifi cations already agreed. Danfoss Randall Limited Ampthill Road,...